Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert® IntelliSlot® Modbus/BACnet IP 194Table 65 Liebert Series 300 UPS - Status and Coil
Data Description Status Coil
Number
of Bits Scale Notes / Units
Automatic Restart Enabled 10001 1 1
Battery Charge Compensation 10046 1
Inverter Ready 10047 1
Load Circuit 1 State 10057 1
Load Circuit 2 State 10058 1
Load Circuit 3 State 10059 1
Load Circuit 4 State 10060 1
Load Circuit 5 State 10061 1
Load Circuit 6 State 10062 1
Load Circuit 7 State 10063 1
Load Circuit 8 State 10064 1
Load Circuit 9 State 10065 1
Load Circuit 10 State 10066 1
Load Circuit 11 State 10067 1
Load Circuit 12 State 10068 1
Load Circuit 13 State 10069 1
Load Circuit 14 State 10070 1
Load Circuit 15 State 10071 1
Load Circuit 16 State 10072 1
Load On Inverter 10073 1
Bypass Active 10074 1
Buck On 10076 1
Replace Battery 10081 1
Battery Under Test 10082 1
Load On Battery 10128 1
Low Battery - Shutdown Imminent 10152 1
Output Overload 10154 1
Over Temperature Warning 10171 1
Battery Over Temperature CB Trip 10172 1
Input Power Supply Fail 10186 1
Input Over Voltage 10187 1
Input Under Voltage 10188 1
Bad Input Frequency 10190 1
Bypass Input Voltage/Frequency Fault 10202 1
Output Under Voltage 10218 1
Output Over Voltage 10219 1
Battery Charger Fail 10234 1
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.