Modbus 485 and Modbus IP Protocols - Battery Monitoring Products
Liebert® IntelliSlot® Modbus/BACnet IP 210
Cell to Cell Temperature Deviation
Threshold
String 1 - 32
33042-33073 1 Units : deg C
Cell to Cell Temperature Deviation
Threshold
String 1 - 32
33074-33105 1 Units : deg F
Cell to Ambient Temperature Deviation
Threshold
String 1 - 32
33106-33137 1 Units : deg C
Cell to Ambient Temperature Deviation
Threshold
String 1 - 32
33138-33169 1 Units : deg F
Battery String Alarm Reset or
Acknowledge
String 1 - 32
43490-43521 1 2 = Reset
4 = Acknowledge
Battery String Time-To-Go
String 1 - 32 32242-32305 2 Units : min
Amp-Hours Remaining in Battery String
String 1 - 32 32306-32337 1 Units : AH
Low Ambient Temperature Global
Threshold
String 1 - 32
32402-32433 1
Scale
: x /
10
Units : deg C
Low Ambient Temperature Global
Threshold
String 1 - 32
32434-32465 1
Scale
: x /
10
Units : deg F
High Ambient Temperature Global
Threshold
String 1 - 32
32466-32497 1
Scale
: x /
10
Units : deg C
High Ambient Temperature Global
Threshold
String 1 - 32
32498-32529 1
Scale
: x /
10
Units : deg F
Battery String Overall Voltage Low
Threshold
String 1 - 32
32530-32561 1
Scale
: x /
10
Units : VDC
Battery String Overall Voltage High
Threshold
String 1 - 32
32562-32593 1
Scale
: x /
10
Units : VDC
Battery String Current High Threshold
String 1 - 32 32594-32625 1 Units : A DC
Battery String Float Current Low
Threshold
String 1 - 32
32626-32657 1 Units : mA DC
Battery String Float Current High
Threshold
String 1 - 32
32658-32689 1 Units : mA DC
Battery String Ripple Current High
Threshold
String 1 - 32
32690-32721 1 Units : A AC
Cell Voltage Low Global Threshold
String 1 - 32 32722-32753 1
Scale
: x /
1000
Units : VDC
Cell Voltage High Global Threshold
String 1 - 32 32754-32785 1
Scale
: x /
1000
Units : VDC
Cell Temperature Low Global Threshold
String 1 - 32 32786-32817 1
Scale
: x /
10
Units : deg C
Table 75 Alber® BDSU - Input and Holding (continued)
Data Description
Input
Register
Holding
Register
# of