BACnet Communications - UPS Systems
Liebert® IntelliSlot® Modbus/BACnet IP 324
Environment
Inlet Air Temperature Analog_Value 126 4291 _1 RD Units: deg C SMS, 1+N,
N+1
Inlet Air Temperature Analog_Value 10126 4291 _1_deg_F RD Units: deg F SMS, 1+N,
N+1
Total System Operating Time Analog_Value 127 4292_1 RD Units: hr CE models
only
System Date and Time Analog_Value 128 4293_1 RW SMS, 1+N,
N+1, SCC
Total kW Hours Saved Analog_Value 129 5446_1 RD Units: kWH SMS, 1+N,
N+1, SCC
System
System Accumulated Energy Analog_Value 140 5789_1 RW Units: kWH SCC, 1+N,
N+1
Module Accumulated Energy Analog_Value 141 5790_1 RW Units: kWH SCC, 1+N,
N+1
Output kWh Reset Timestamp Analog_Value 142 5791_1 RD SMS, 1+N,
N+1, SCC
Output Peak kW Demand Analog_Value 143 5793_1 RD Units: kW SMS, 1+N,
N+1, SCC
Output Peak kW Demand Hist Analog_Value 144 5794_1 RD Units: kW SMS, 1+N,
N+1, SCC
Peak kW Demand Timestamp Analog_Value 145 5797_1 RD SMS, 1+N,
N+1, SCC
Ratings
Bypass Nominal Voltage Analog_Value 156 4259_1 RD Units: VAC SMS, 1+N,
SCC
System Input Nominal Voltage Analog_Value 157 4102_1 RD Units: VAC SMS, 1+N,
N+1
System Input Nominal Frequency Analog_Value 158 4103_1 RD Units: Hz SMS, 1+N,
N+1
System Output Nominal Voltage Analog_Value 159 4260_1 RD Units: VAC SMS, 1+N,
N+1, SCC
System Output Nominal Frequency Analog_Value 160 4261_1 RD Units: Hz SMS, 1+N,
N+1, SCC
Battery Cell Count - Lead Acid Analog_Value 161 4262_1 RD SMS, 1+N,
N+1
Battery Cell Count-Nickel Cadmium Analog_Value 16 2 4263_1 RD SMS, 1+N,
N+1
Output Apparent Power Rating Ana log_Value 163 4264_1 RD Units: kVA SMS, 1+N,
N+1
Output Real Power Rating Analog_Value 164 4265 _1 RD Units: kW SMS, 1+N,
N+1
System UPS Module Count Analog_Value 165 4800_1 RD SMS, 1+N,
SCC
System Output Maximum Amp Rating Analog_Value 166 4267_1 RD Units: A AC 1+N, SCC
Table 107 Liebert NXL - 60Hz, UL version (Model 40) - Analog Data (continued)
Data Label Object Type Instance
Object
Name Access Notes
Liebert
NXL Type