Modbus 485 and Modbus IP Protocols - UPS Systems
155 Liebert® IntelliSlot® Modbus/BACnet IP
Battery Volts for Cabinet 4 30361 1 VDC N+1, 1+N,
1+1, SMS
Battery Volts for Cabinet 5 30362 1 VDC N+1, 1+N,
1+1, SMS
Battery Volts for Cabinet 6 30363 1 VDC N+1, 1+N,
1+1, SMS
Battery Volts for Cabinet 7 30364 1 VDC N+1, 1+N,
1+1, SMS
Battery Volts for Cabinet 8 30365 1 VDC N+1, 1+N,
1+1, SMS
Battery Temperature for Cabinet 1 30366 1 deg C N+1, 1+N,
1+1, SMS
Battery Temperature for Cabinet 2 30367 1 deg C N+1, 1+N,
1+1, SMS
Battery Temperature for Cabinet 3 30368 1 deg C N+1, 1+N,
1+1, SMS
Battery Temperature for Cabinet 4 30369 1 deg C N+1, 1+N,
1+1, SMS
Battery Temperature for Cabinet 5 30370 1 deg C N+1, 1+N,
1+1, SMS
Battery Temperature for Cabinet 6 30371 1 deg C N+1, 1+N,
1+1, SMS
Battery Temperature for Cabinet 7 30372 1 deg C N+1, 1+N,
1+1, SMS
Battery Temperature for Cabinet 8 30373 1 deg C N+1, 1+N,
1+1, SMS
Backfeed Breaker 30374 1
0 = Open
1 = Close
2 = Not Installed
N+1, 1+N,
1+1, SMS
SBS Load Disconnect 30375 1
0 = Open
1 = Close
2 = Not Installed
Deprecated
Input Breaker (CB1/RIB) 30376 1
0 = Open
1 = Close
2 = Not Installed
SCC, N+1,
1+N, 1+1, SMS
Trap Filter Disconnect 30377 1
0 = Open
1 = Close
2 = Not Installed
SCC, N+1,
1+N, 1+1, SMS
Output Breaker (CB2/IOB) 30378 1
0 = Open
1 = Close
2 = Not Installed
SCC, N+1,
1+N, 1+1, SMS
Internal Bypass Breaker (CB3) 30379 1
0 = Open
1 = Close
2 = Not Installed
Deprecated
Bypass Isolation Breaker (BIB) 30380 1
0 = Open
1 = Close
2 = Not Installed
SCC, 1+N,
1+1, SMS
Rectifier Feed Breaker (RFB) 30381 1
0 = Open
1 = Close
2 = Not Installed
SCC, SMS
Maintenance Bypass Breaker (MBB) 30382 1
0 = Open
1 = Close
2 = Not Installed
SCC, 1+N,
1+1, SMS
Table 56 Liebert NXL - 60Hz, UL version (Model 40) - Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Regs Scale Units / Notes
NXL
Types