Modbus 485 and Modbus IP Protocols - Thermal Management Products
19 Liebert® IntelliSlot® Modbus/BACnet IP
Compressor Low Suction Pressure - Event
Type 1 30337 40337 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Compressor Low Suction Pressure - Event
Type 2 30338 40338 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Compressor Pump Down Issue - Event
Control 1 30339 40339 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Compressor Pump Down Issue - Event
Control 2 30340 40340 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Compressor Pump Down Issue - Event
Type 1 30341 40341 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Compressor Pump Down Issue - Event
Type 2 30342 40342 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Compressor Short Cycle - Event Control 1 30343 40343 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Compressor Short Cycle - Event Control 2 30344 40344 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Compressor Short Cycle - Event Type 1 30345 40345 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Compressor Short Cycle - Event Type 2 30346 40346 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Compressor Thermal Overload - Event
Control 1 30347 40347 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Compressor Thermal Overload - Event
Control 2 30348 40348 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Compressor Thermal Overload - Event
Type 1 30349 40349 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Compressor Thermal Overload - Event
Type 2 30350 40350 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Dig Scroll Comp Discharge Over Temp -
Event Ctrl 1 30351 40351 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Dig Scroll Comp Discharge Over Temp -
Event Ctrl 2 30352 40352 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Dig Scroll Comp Discharge Over Temp -
Event Type 1 30353 40353 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Dig Scroll Comp Discharge Over Temp -
Event Type 2 30354 40354 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Ext Air Sensor A High Humidity - Event
Control 30355 40355 1 0 = disabled
1 = enabled 1, 2, 3, 4, 5, 6
Ext Air Sensor A High Humidity - Event
Type 30356 40356 1
0 = Message
1 = Warning
2 = Alarm
1, 2, 3, 4, 5, 6
Table 8 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3,
Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX - Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra
Notes