BACnet Communications - Thermal Management Products
273 Liebert® IntelliSlot® Modbus/BACnet IPTable 88 Liebert HPC - Analog Data
Controller Liebert iCOM® v4
Data Label Object Type Instance
Object
Name Access Notes
Extra
Notes
Compressors
Compressor Shut Down - Ambient Air Low
Temp Li mi t Analog_Value 1 5262_1 RW Units: deg C 1, 2
Compressor Shut Down - Ambient Air Low
Temp Li mi t Analog_Value 10001 5262_1_deg_F RW Units: deg F 1, 2
Compressors - Compressor 1
Compressor Head Pressure Analog_Value 12 5266_1_1 RD Units: bar 1, 2
Compressor Hours Analog_Value 13 5267_1_1 RW Units: hr 1, 2
Compressor Hours Threshold Analog_Value 14 5268_1_1 RW Units: hr 1, 2
Compressors - Compressor 2
Compressor Head Pressure Analog_Value 25 5266_1_2 RD Units: bar 1, 2
Compressor Hours Analog_Value 26 5267_1_2 RW Units: hr 1, 2
Compressor Hours Threshold Analog_Value 27 5268_1_2 RW Units: hr 1, 2
Compressors - Compressor 4
Compressor Head Pressure Analog_Value 215 5266_1_4 RD Units: bar 2
Compressor Hours Analog_Value 216 5267_1_4 RW Units: hr 2
Compressor Hours Threshold Analog_Value 217 52 68_1_4 RW Units: hr 2
Condenser 1
Condenser Fan Speed Analog_Value 38 5276_1 RD Units: % 1, 2
Condenser 2
Condenser Fan Speed Analog_Value 49 5276_2 RD Units: % 1, 2
Condenser 4
Condenser Fan Speed Analog_Value 55 5276_4 RD Units: % 2
Fluid
Fluid Pressure Analog_Value 60 5279_1 RD Units: bar 1, 2
Fluid Cooling Proportional Band Analog_ Value 61 5281_1 RW Units: deg C 1, 2
Fluid Cooling Proportional Band Analog_Value 1006 1 5281_1_deg_F RW Units: deg F 1, 2
Fluid - Supply (Outlet) Fluid
Supply Fluid Temp Set Point 1 Analog_Value 72 5283_1_1 RW Units: deg C 1, 2
Supply Fluid Temp Set Point 1 Analog_Value 10072 5283_1_1_deg_F RW Units: deg F 1, 2
Supply Fluid Temp Set Point 2 Analog_Value 73 5284_1_1 RW Units: deg C 1, 2
Supply Fluid Temp Set Point 2 Analog_Value 10073 5284_1_1_deg_F RW Units: deg F 1, 2
Supply Fluid Over Temp Alarm Threshold Analog_Value 74 5285_1_1 RW Units: deg C 1, 2
Supply Fluid Over Temp Alarm Threshold Analog_Value 10074 5285_1_1_deg_F RW Units: deg F 1, 2
Supply Fluid Over Temp Warning Threshold Analog_Value 75 46 44_1_1 RW Units: deg C 1, 2
Supply Fluid Over Temp Warning Threshold Analog_Value 10075 4644_1_1_deg_F RW Units: deg F 1, 2
Supply Fluid Under Temp Warning
Threshold Analog_Value 76 5286_1_1 RW Units: deg C 1, 2
Supply Fluid Under Temp Warning
Threshold Analog_Value 10076 5286_1_1_deg_F RW Units: deg F 1, 2
Supply Fluid Under Temp Alarm Threshold Analog_Value 77 5287_1_1 RW Units: deg C 1, 2
Supply Fluid Under Temp Alarm Threshold Analog_Value 10077 5287_1_1_deg_F RW Units: deg F 1, 2
Pumps - Pump 1
Pump Hours Analog_Value 88 52 98_1_1 RW Units: hr 1, 2
Pump Hours Threshold Analog_Value 89 5299_1_1 RW Units: hr 1, 2
Pumps - Pump 2
Pump Hours Analog_Value 100 5298_1_2 RW Units: hr 1, 2
Pump Hours Threshold Analog_Value 101 5299_1_2 RW Units: hr 1, 2