BACnet Communications - Thermal Management Products
293 Liebert® IntelliSlot® Modbus/BACnet IP
Ext Remote Shutdown Unit is shut down by a remote signal.
Ext System Condensation Detected -
Event Control
Enable/disable the activation of the [Ext System Condensation Detected]
event. If set to 'disabled', the event will not be annunciated. This implies that
the event will not be placed in any active event list or in any event history list.
Ext System Condensation Detected -
Event Type The event type for the [Ext System Condensation Detected] event.
Ext System Condensation Detected External system condensation detected.
Fan Button Control Enable or disable the buttons from controlling the state of the fans.
Fan Economy Mode Mode in which system secondary fans are to be controlled.
Fan Issue - Event Control
Enable/disable the activation of the [Fan Issue] event. If set to 'disabled', the
event will not be annunciated. This implies that the event will not be placed in
any active event list or in any event history list.
Fan Issue - Event Type The event type for the [Fan Issue] event.
Fan Issue One or more fans are not operating within their operational parameters.
Fan On/Off Control Turn system fans on or off.
Fan State Current operational state of a group of fans.
Hot Aisle Over Temp Threshold Upper threshold value used in the [Hot Aisle Temp Out of Range] event.
Hot Aisle Temp Out of Range The air temperature in the Hot aisle is either above [Hot Aisle Over Temp
Threshold] or below [Hot Aisle Under Temp Threshold].
Hot Aisle Under Temp Threshold Lower threshold value used in the [Hot Aisle Temp Out of Range] event.
Hot Gas Solenoid Valve 1 Position Hot gas solenoid valve 1 position.
Hot Gas Solenoid Valve 2 Position Hot gas solenoid valve 2 position.
Hot Gas Valve 1 Open Position Hot gas valve 1 op en position.
Hot Gas Valve 2 Open Position Hot gas valve 2 op en position.
Maintenance Completed Maintenance has been completed on the unit.
Maintenance Due The calculated maintenance date has been reached.
Maintenance Ramp The ratio of operations performed to the calculated operations available
between maintenance intervals.
Master Unit Communication Lost Communication with master unit has been lost.
Minimum Room Temperature Set Point Minimum desired room air temperature. If the room air temperature falls below
this set point, the unit will reduce the cooling.
Primary Fan Group State Current operational state of the primary fan group.
Pump 1 Loss of Flow - Event Control
Enable/disable the activation of the [Pump 1 Loss of Flow] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Pump 1 Loss of Flow - Event Type The event type for the [Pump 1 Loss of Flow] event.
Pump 1 Loss of Flow Loss of flow is detected in pump 1. The loss of flow condition occurs when no
differential pressure is detected across the pump.
Pump 1 State Pump 1 operational state.
Pump 2 Loss of Flow - Event Control
Enable/disable the activation of the [Pump 2 Loss of Flow] event. If set to
'disabled', the event will not be annunciated. This implies that the event will not
be placed in any active event list or in any event history list.
Pump 2 Loss of Flow - Event Type The event type for the [Pump 2 Loss of Flow] event.
Pump 2 Loss of Flow Loss of flow is detected in pump 2. The loss of flow condition occurs when no
differential pressure is detected across the pump.
Pump 2 State Pump 2 operational state.
Pump Hours Exceeded [Pump Hours] has exceede d [Pump Hours Threshold].
Pump Hours Threshold Threshold value used in the [Pump Hours Exceeded] event.
Table 95 Liebert XDP, Liebert XDC - Glossary (continued)
Data Label Data Description