Modbus 485 and Modbus IP Protocols - Thermal Management Products
Liebert® IntelliSlot® Modbus/BACnet IP 24
Condenser Low Noise Mode Start Time 30681 40681 2 Seconds since Midnight 3, 4, 5, 6
Condenser Low Noise Mode Stop Time 30683 40683 2 Seconds since Midnight 3, 4, 5, 6
Pump Hours 1 30685 40685 2 hr 5
Pump Hours 2 30687 40687 2 hr 5
System Input RMS A-N 1 30800 1 10 VAC 6
System Input RMS A-N 2 30801 1 10 VAC 6
System Input RMS A-N 3 30802 1 10 VAC 6
System Input RMS A-N 4 30803 1 10 VAC 6
System Input RMS A-N 5 30804 1 10 VAC 6
System Input RMS A-N 6 30805 1 10 VAC 6
System Input RMS B-N 1 30810 1 10 VAC 6
System Input RMS B-N 2 30811 1 10 VAC 6
System Input RMS B-N 3 30812 1 10 VAC 6
System Input RMS B-N 4 30813 1 10 VAC 6
System Input RMS B-N 5 30814 1 10 VAC 6
System Input RMS B-N 6 30815 1 10 VAC 6
System Input RMS C-N 1 30820 1 10 VAC 6
System Input RMS C-N 2 30821 1 10 VAC 6
System Input RMS C-N 3 30822 1 10 VAC 6
System Input RMS C-N 4 30823 1 10 VAC 6
System Input RMS C-N 5 30824 1 10 VAC 6
System Input RMS C-N 6 30825 1 10 VAC 6
System Input RMS Current Phase A 1 30830 1 10 A AC 6
System Input RMS Current Phase A 2 30831 1 10 A AC 6
System Input RMS Current Phase A 3 30832 1 10 A AC 6
System Input RMS Current Phase A 4 30833 1 10 A AC 6
System Input RMS Current Phase A 5 30834 1 10 A AC 6
System Input RMS Current Phase A 6 30835 1 10 A AC 6
System Input RMS Current Phase B 1 30840 1 10 A AC 6
System Input RMS Current Phase B 2 30841 1 10 A AC 6
System Input RMS Current Phase B 3 30842 1 10 A AC 6
System Input RMS Current Phase B 4 30843 1 10 A AC 6
System Input RMS Current Phase B 5 30844 1 10 A AC 6
System Input RMS Current Phase B 6 30845 1 10 A AC 6
System Input RMS Current Phase C 1 30850 1 10 A AC 6
System Input RMS Current Phase C 2 30851 1 10 A AC 6
System Input RMS Current Phase C 3 30852 1 10 A AC 6
System Input RMS Current Phase C 4 30853 1 10 A AC 6
System Input RMS Current Phase C 5 30854 1 10 A AC 6
System Input RMS Current Phase C 6 30855 1 10 A AC 6
Table 8 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3,
Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX - Input and Holding (continued)
Controller Liebert iCOM v4
Data Label
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Extra