Modbus 485 and Modbus IP Protocols - UPS Systems
161 Liebert® IntelliSlot® Modbus/BACnet IP
MMS Module Total kVA Output 30651 1 Units : kVA SCC
MMS Module DC Bus Voltage 30652 1 Units : VDC SCC
MMS Module Battery Current 30653 1 Un its : A DC SCC
MMS Module Battery Time
Remaining 30654 1 Units : min SCC
Intelligent Paralleling
Intelligent Parallel Operation
State 30658 1 — 0 = disabled
1 = enabled
N+1, 1+N,
SCC
Intelligent Parallel Mode 30659 1 1 = Disconnect
(More Efficient)
N+1,
1+N,
SCC
Intelligent Paralleling Shutdown
Delay 30660 1 Units : min N+1, 1+N,
SCC
Intelligent Parallel Minimum
Redundancy 30661 — 1 — N+1, 1+N,
SCC
Intelligent Parallel Maximum
Time in Standby 30662 1 Units : day N+1, 1+N,
SCC
ECO Mode
ECO Mode Operation State 30666 40666 1 0 = disabled
1 = enabled
SMS, 1+N,
SCC
Continuous Operation - ECO Mode 30667 1 0 = disabled
1 = enabled
SMS, 1+N,
SCC
Maximum Auto Suspensions - ECO
Mode 30668 — 1 — SMS, 1+N,
SCC
Restart Delay - ECO Mode 30669 1 Units : min SMS, 1+N,
SCC
Time Remaining - ECO Mode 30670 1 Units : min SMS, 1+N,
SCC
EcoModeSchedule 1
Schedule Operation State - ECO
Mode 30674 — 1 — 0 = disabled
1 = enabled
SMS, 1+N,
SCC
Schedule Action - ECO Mode 30675 1 0 = stop
1 = start
SMS, 1+N,
SCC
Schedule Day of Week - ECO
Mode 30676 — 1 —
0 = Unknown
1 = Monday
2 = Tuesday
3 = Wednesday
4 = Thursday
5 = Friday
6 = Saturday
7 = Sunday
SMS, 1+N,
SCC
Schedule Hour - ECO Mode 30677 1 Units : hr SMS, 1+N,
SCC
Schedule Minute - ECO Mode 30678 1 Units : min SMS, 1+N,
SCC
Table 56 Liebert NXL - 60Hz, UL version (Model 40) - Input and Holding (continued)
Data Label
Input
Register
Holding
Register
# of
Regs Scale Units / Notes
NXL
Types