Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
95 Liebert® IntelliSlot® Modbus/BACnet IP
Alarm Points Discrete alarm objects available;
use auto-discover for this unit
Communications 40 289 1 Bit 0
Output Undervoltage 40289 1 Bit 1
Output Overvoltage 40289 1 Bit 2
Output Overcurrent 40289 1 Bit 3
Frequency Deviation 40289 1 Bit 4
Ground Overcurrent 40289 1 Bit 5
Transformer Overtemp 40289 1 Bit 6
Ground Fault 40289 1 Bit 7
Ground Failure 40289 1 Bit 8
Liquid Detected 40289 1 Bit 9
Security Alarm 40289 1 Bit 10
Phase Rotation/Loss 40290 1 Bit 0
Datawave Overtemperature 40290 1 Bit 1
Emergency Shutdown 40290 1 Bit 2
Load On Bypass 40290 1 Bit 3
Local Alarm #1 40290 1 Bit 4
Local Alarm #2 40290 1 Bit 5
Output Voltage THD 40290 1 Bit 6
Custom Alarm #1 40290 1 Bit 7
Custom Alarm #2 40290 1 Bit 8
Setpoints (View)
None 1 —
Control Points (Set)
None 1 —
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 33 Liebert Datawave, Liebert FPC, Liebert PPC - Input and Holding - PMP, PM2 Options for Liebert FPC and Liebert PPC (continued)
Controller Power Monitoring Panel - PMP, PM2 Options for Liebert FPC and Liebert PPC
Liebert Products
Liebert Datawave
Liebert FPC
Liebert PPC
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units