BACnet Communications - UPS Systems
Liebert® IntelliSlot® Modbus/BACnet IP 328
System
UPS Module Type MultiState_Value 84 4303_1 RD
1 = Single Module
System
2 = Module (1 + 1)
3 = Module (1 + N)
4 = Module (N + 1)
5 = System Control
Cabinet
6 = Main Static Switch
SMS, 1+N,
N+1, SCC
Bypass Input Wire
Configuration MultiState_Value 85 4304_1 RD
1 = Two Wire (single
phase + return)
2 = Two Wire (2 phase,
no neutral)
3 = Three Wire (2
phase + neutral)
4 = Three Wire (3
phase, no neutral)
5 = Four Wire (3
phases + neutral)
SMS, 1+N,
SCC
Output Wire Configuration MultiState_Value 86 4305_1 RD
1 = Two Wire (single
phase + return)
2 = Two Wire (2 phase,
no neutral)
3 = Three Wire (2
phase + neutral)
4 = Three Wire (3
phase, no neutral)
5 = Four Wire (3
phases + neutral)
SMS, 1+N,
N+1, SCC
Static Switch Type MultiState_Value 87 4306_1 RD
1 = Not Applicable
2 = Continuous Duty
3 = Momentary Duty
SMS, 1+N,
SCC
Configuration Description MultiState_Value 88 4751_1 RD
1 = Single Module
System 33
2 = Single Module
System 34
3 = Single Module
System 44
4 = 1+1 33
5 = 1+1 34
6 = 1+1 44
7 = 1+N 33
8 = 1+N 34
9 = 1+N 44
10 = N+1 33
11 = N+1 34
12 = N+1 44
13 = SCC w/
Continuous Duty SS 33
14 = SCC w/
Continuous Duty SS 44
15 = SCC w/
Momentary Duty SS
16 = Main Static Switch
SMS, 1+N,
N+1, SCC
UPS System Output Source MultiState_Value 89 4752_1 RD
1 = off
2 = Normal
3 = Bypass
4 = Maintenance
Bypass
SMS, 1+N,
SCC
System Input Power Source MultiState_Value 90 4318_1 RD
1 = None
2 = Utility (mains)
3 = Generator
SMS, 1+N,
N+1, SCC
Table 108 Liebert NXL - 60Hz, UL version (Model 40) - Multistate Data (continued)
Data Label
Object
Type Instance
Object
Name Access Notes
Liebert
NXL Type