BACnet Communications - Thermal Management Products
Liebert® IntelliSlot® Modbus/BACnet IP 224
Supply Chilled Water Over Temp Binary_Value 271 4626_1 RD Active on Alarm 1, 2, 3,
4, 5, 6
Unit Code Missing Binary_Value 272 5418_1 RD Active on Alarm 1, 2, 3,
4, 5, 6
Unit Communication Lost Binary_Value 273 5419_1 RD Active on Alarm 1, 2, 3,
4, 5, 6
Water Leakage Detector Sensor Issue Binary_Value 274 5114_1 RD Active on Alarm 1, 2, 3,
4, 5, 6
Water Under Floor Binary_Value 275 4723_1 RD Active on Alarm 1, 2, 3,
4, 5, 6
Ext Over Temperature Binary_Value 276 5104_1 RD Active on Alarm 1, 2, 3,
4, 5, 6
External Fire Detected Binary_Value 277 5108_1 RD Active on Alarm 1, 2, 3,
4, 5, 6
Unspecified General Event Binary_Value 278 5588_1 RD Active on Alarm 2, 3, 4,
5, 6
Temperature Control Sensor Issue Binary_Value 279 5617_1 RD Active on Alarm 2, 3, 4,
5, 6
Airflow Sensor Issue Binary_Value 280 5906_1 RD Active on Alarm 5, 6
Ext Air Damper Position Issue Binary_Value 281 5907_1 RD Active on Alarm 5, 6
Ext Power Source A Failure Binary_Value 282 5908_1 RD Active on Alarm 5, 6
Ext Power Source B Failure Binary_Value 283 5909_1 RD Active on Alarm 5, 6
Mixed Mode Lockout Binary_Value 284 5924_1 RD Active on Alarm 5
System Events - Chilled Water Valve 1
Chilled Water Control Valve Failure Binary_Value 288 4703_1_1 RD Active on Alarm 1, 2, 3,
4, 5, 6
System Events - Chilled Water Valve 2
Chilled Water Control Valve Failure Binary_Value 299 4703_1_2 RD Active on Alarm 1, 2, 3,
4, 5, 6
System Events - Messages
Unit Off Binary_Value 310 5110_1_1 RD Active on Alarm 1, 2, 3,
4, 5, 6
Unit On Binary_Value 311 5109_1_1 RD Active on Alarm 1, 2, 3,
4, 5, 6
Unit Partial Shutdown Binary_Value 312 5112_1_1 RD Active on Alarm 1, 2, 3,
4, 5, 6
Unit Shutdown Binary_Value 313 5113_1_1 RD Active on Alarm 1, 2, 3,
4, 5, 6
Unit Standby Binary_Value 314 5111_1_1 RD Active on Alarm 1, 2, 3,
4, 5, 6
Maintenance Due Binary_Value 315 5116_1_1 RD Active on Alarm 1, 2, 3,
4, 5, 6
Maintenance Completed Binary_Value 316 5117_1_1 RD Active on Alarm 1, 2, 3,
4, 5, 6
System Events - Liebrt iCOM-DO Board 1
Digital Output Board Not Detected Binary_Value 327 5417_1_1 RD Active on Alarm 1, 2, 3,
4, 5, 6
System Events - iCOM DO Board 2
Digital Output Board Not Detected Binary_Value 338 5417_1_2 RD Active on Alarm 1, 2, 3,
4, 5, 6
Table 76 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3,
Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX - Binary Data (continued)
Controller Liebert iCOM® v4
Data Description Object Type Instance
Object
Name Access Notes
Extra
Notes