Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert® IntelliSlot® Modbus/BACnet IP 200Table 70 Liebert Series 610 SCC UPS - Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units
Number of Input Lines 30004 40004 1 Bits 12 - 15
Number of Bypass Lines 30004 40004 1 Bits 4 - 7
Number of Output Lines 30004 40004 1 Bits 8 - 11
Nominal Power Rating 30021 40021 2 VA
Nominal Input Voltage 30027 40027 1 V
Nominal Output Voltage 30028 40028 1 V
Nominal Static Bypass Switch Voltage 30029 40029 1 V
Nominal Output Frequency 30032 40032 1 10 Hz
Nominal Power Factor 30033 40033 1 100 -
Silence Alarm 40101 1 -
Load (Apparent Power) 30102 2 VA
Load (Real Power) 30104 2 W
Load / Capacity 30106 1 %
Output Frequency 30108 1 10 Hz
Bypass Frequency 30109 1 10 Hz
Input Voltage L1 30153 1 V
Bypass Voltage L1 30159 1 V
Bypass Current L1 30160 1 A
Output Voltage L1 30163 1 V
Output Current L1 30164 1 A
Input Voltage L2 30203 1 V
Bypass Voltage L2 30209 1 V
Bypass Current L2 30210 1 A
Output Voltage L2 30213 1 V
Output Current L2 30214 1 A
Input Voltage L3 30253 1 V
Bypass Voltage L3 30259 1 V
Bypass Current L3 30260 1 A
Output Voltage L3 30263 1 V
Output Current L3 30264 1 A
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.