Modbus 485 and Modbus IP Protocols - UPS Systems
145 Liebert® IntelliSlot® Modbus/BACnet IP
Table 54 Liebert NX 225-600kVA UPS - Input and Holding3
Data Description Input
Holding
Register
# of
Reg Scale Notes/Units
Identification
Modbus Protocol Version 40002 1 XX.YY
Manufacturer 40003 1 0 = Chloride
Model 40004 1 8 = 80Net
UPS Software 1 Version 40005 1 HH Major – LL Minor
UPS Software 1 Date Year 40006 1
UPS Software 1 Date Month 40007 1
UPS Software 1 Date Day 40008 1
UPS Software 1 Code 40009 1 10HXXXXX code
UPS Software 2 Version 40010 1 HH Major – LL Minor
UPS Software 2 Date Year 40011 1
UPS Software 2 Date Month 40012 1
UPS Software 2 Date Day 40013 1
UPS Software 2 Code 40014 1 10HXXXXX code
Battery
Battery Status 40020 1
1 = Unknown
2 = Battery Normal
3 = Battery Low
4 = Battery Depleted
Seconds On Battery 40021 1 Units: Seconds
Estimated Seconds Remaining 40022 1 Units: Seconds
Estimated Charge Remaining 40023 1 Units: %
Battery Voltage 40024 1 10 Units: V
Battery Current 40025 1 10 Units: A
Battery Temperature 40026 1 Units: Deg C
Input
Line Bads 40032 1
Frequency 40033 1 10 Units: Hz
Number Lines 40034 1
Voltage L1 40035 1 Units: V
Voltage L2 40036 1 Units: V
Voltage L3 40037 1 Units: V
Current L1 40038 1 10 Units: Amps
Current L2 40039 1 10 Units: A
Current L3 40040 1 10 Units: A
Real Power L1 40041 1 10 Units: kW
Real Power L2 40042 1 10 Units: kW
Real Power L3 40043 1 10 Units: kW
DC Voltage 40044 1 Units: V