Modbus 485 and Modbus IP Protocols - Thermal Management Products
89 Liebert® IntelliSlot® Modbus/BACnet IP
EPO Shutdown 40291 1 Bit 8
Local Alarm 3 43291 1 Bit 9
Local Alarm 4 40291 1 Bit 10
Run Times (View)
Compressor 1 Run Hours 40019 1
Compressor 2 Run Hours 40020 1
Glycol Run Hours 1
Fan Motor Run Hours 40021 1
Humidifier Run Hours 40022 1
Reheat 1 Run Hours 1
Reheat 2 Run Hours 1
Reheat 3 Run Hours 1
Chilled H2O Valve Run Hours 1
Setpoints (View)
Temperature Setpoint 40010 1 (R/W)
Temperature Tolerance 40011 1 (R/W)
Humidity Setpoint 40012 1 (R/W)
Humidity Tolerance 40013 1 (R/W)
High Temperature Alarm Setpoint 40014 1 (R/W)
Low Temp Alarm Setpoint 4001 5 1 (R/W)
High Humidity Alarm Setpoint 40016 1 (R/W)
Low Humidity Alarm Setpoint 40017 1 (R/W)
Winter Start Delay 40028 1 Minutes (R/W)
Auto Flush Rate 40029 1 % (R/W)
Chill Water Flush Rate 40030 1 Hours (R/W)
Auto Restart Delay 40031 1 0.1 minute (R/W)
Control Points (Set)
Unit Status (On / Off) 40018 1 1=On / 0=Off (R/W)
Unit On / Off 40349 1 Bit 0 On=unit Off
Bit 1 On=unit On (W)
Temperature Setpoint 40350 1 (W)
Temperature Tolerance 40350 1 1000 (W)
Humidity Setpoint 40351 1 - (W)
Humidity Tolerance 40351 1 1000 (W)
Reheat Lockout 40349 1 Bit 2 On=RH Off
Bit 3 On=RH On
Humidifier Lockout 40349 1 Bit 4 On=HL Off
Bit 5 On=HL On
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 30 Liebert Mini-Mate2 8 Ton - Input and Holding - L8T (continued)
Controller L8T
Liebert Products Liebert Mini-Mate2 8 Ton
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Scale Notes / Units