Modbus 485 and Modbus IP Protocols - Thermal Management Products
87 Liebert® IntelliSlot® Modbus/BACnet IP
Setpoints (View)
Temperature — 40010 1 — —
Temp Tolerance 40011 1
Humidity — 40012 1
Humidity Tolerance 40013 1
High Temperature Alarm 40014 1
Low Temperature Alarm 40015 1
High Humidity Alarm 40016 1
Low Humidity Alarm 40017 1
Chill Water Flush Rate 40025 1 Hours (R/W)
Auto Restart Delay 40026 1 0.1 minute (R/W)
Control Points (Set)
Unit On/Off 40018 1 1=On / 0=Off (R/W)
Remote On/Off 40349 1 Bit 0 On=unit Off
Bit 1 On=unit On (W)
Temperature Setpoint 40350 1 (W)
Temperature Tolerance 40350 1 1 000 Multiply desired value by 1000
(Modbus only) 0=No Change (W)
Humidity Setpoint 40351 1 - (W)
Humidity Tolerance 40351 1 1000 Multiply desired value by 1000
(Modbus only) 0=No Change (W)
Trendable Points (Set)
Temperature 1 —
Humidity 1 —
Reports
Trend 1 —
Status 1 —
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 29 Liebert DataMate, Liebert Mini-Mate2 - Input and Holding - MM2 (continued)
Controller MM2
Liebert Products Liebert DataMate
Liebert Mini-Mate2
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg. Sca le Notes / Units