BACnet Communications - Thermal Management Products
243 Liebert® IntelliSlot® Modbus/BACnet IP
Reheat
Reheater Lockout MultiState_Value 316 5582_1 RW 1 = disabled
2 = enabled
2, 3, 4,
5, 6
Humidifier
Humidifier Lockout MultiState_Value 328 5583 _1 RW 1 = disabled
2 = enabled
2, 3, 4,
5, 6
Air Economizer
Air Economizer Availability MultiState_Value 340 5599_1 RD 1 = Not Available
2 = Available
2, 3, 4,
5, 6
Air Economizer Control Source MultiState_Value 341 5602_1 RW
1 = disabled
2 = internal
3 = external
2, 3, 4,
5, 6
Global Condensers - GC Low Noise Mode
Condenser Low Noise Mode
State MultiState_Value 374 5546_1_1 RD
1 = Inactive
2 = Active
(Interval)
3 = Active (Full
Day)
3, 4, 5,
6
Condenser Low Noise Mode
Schedule Control MultiState_Value 375 5547_1_1 RW 1 = disabled
2 = enabled
3, 4, 5,
6
Table 81 Extra Notes to Table80
Number Description
1This point is supported on:
iCOM controller version 1.04.042.STD
2
This point is supported on:
iCOM controller version 2.00.11R for US
iCOM controller version 2.00.12R (for Japan and China – language corrections only)
3This point is supported on:
iCOM controller version 2.01.23R
4This point is supported on:
iCOM controller version 2.02.16R
5This point is supported on:
iCOM controller version 2.03.27.07R
6This point is supported on:
iCOM controller version 2.01.32.02R
Table 80 Liebert Challenger 3000, Liebert Challenger ITR, Liebert CW, Liebert Deluxe System/3,
Liebert DS, Liebert DSE, Liebert HPM, Liebert PeX - Multistate Data (continued)
Data Label Object Type Instance Object Name Access Notes