Modbus 485 and Modbus IP Protocols - Battery Monitoring Products

207 Liebert® IntelliSlot® Modbus/BACnet IP

3.4 Battery Monitoring Products

Table 74 Alber® BDSU - Status and Coil

Data Description Status Coil
Number
of Bits Notes / Units
Battery Entity
Battery Discharging
Battery 1 - 32 10001-10032 1 Active on Alarm
String Entity
High Ambient Temperature
String 1 - 32 10033-10064 1 Active on Alarm
Low Ambient Temperature
String 1 - 32 10065-10096 1 Active on Alarm
Low Ambient Temperature Probe Two
String 1 - 32 10097-10128 1 Active on Alarm
High Ambient Temperature Probe Two
String 1 - 32 10129-10160 1 Active on Alarm
Low Overall Voltage
String 1 - 32 10161-10192 1 Active on Alarm
High Overall Voltage
String 1 - 32 10193-10224 1 Active on Alarm
High Battery String Current
String 1 - 32 10225-10256 1 Active on Alarm
Low Battery String Float Current
String 1 - 32 10257-10288 1 Active on Alarm
High Battery String Float Current
String 1 - 32 10289-10320 1 Active on Alarm
High Battery String Ripple Current
String 1 - 32 10321-10352 1 Active on Alarm
Battery String Discharge Detected
String 1 - 32 10353-10384 1 Active on Alarm
Maximum Discharge Time Exceeded
String 1 - 32 10385-10416 1 Active on Alarm
Discharge Low Overall Voltage
String 1 - 32 10417-10448 1 Active on Alarm
Discharge Low Cell Voltage
String 1 - 32 10449-10480 1 Active on Alarm
Discharge High Battery String Current
String 1 - 32 10481-10512 1 Active on Alarm
Excessive Cell to Cell Temperature Deviation
String 1 - 32 10513-10544 1 Active on Alarm
Excessive Cell to Ambient Temperature Deviation
String 1 - 32 10545-10576 1 Active on Alarm
Thermal Runaway Detected
String 1 - 32 10577-10608 1 Active on Alarm
Battery String Equalize
String 1 - 32 10609-10640 1 Active on Alarm
Battery String Offline
String 1 - 32 10641-10672 1 Active on Alarm
Thermal Runaway Cell to Ambient Temperature Event
String 1 - 32 13233-13264 1 Active on Alarm
Thermal Runaway Cell to Cell Temperature Event
String 1 - 32 13265-13296 1 Active on Alarm