Backing Up and Restoring Rack and Power Manager

It is always preferable to restore from a full system backup. In the event that a full system backup is not possible, all settings, configurations and devices for HP Rack and Power Manager are stored in the DEVICEDB1.GDB, DB.INI and ISC4.GDB files. At a minimum, it is best to ensure that these files are backed up on a regular basis. If the HP Rack and Power Manager Management Server must be recovered and a full system backup is not available, the Management Server can be recovered using the following steps:

1.Install a new copy of HP Rack and Power Manager.

2.Stop these services or processes in the following order:

Friendly Name

Windows Service Name

Linux Process Name

a. HP Management Server

HP Management Server

HP Service Manager

 

 

HP Device Manager

 

 

HP Discovery Manager

 

 

HP Rack Manager

b. Firebird Guardian Service

InterBaseGuardian

ibguard

c. Firebird Server (if not already stopped)

InterBaseServer

ibserver

3.Replace the DEVICESDB1.GDB, DB.INI and ISC4.GDB files in the directory in which HP Rack and Power Manager installed them.

4.Restart services or processes in the following order:

a.Firebird Guardian Service

b.Firebird Server (if not already started)

c.HP Management Server

5.After the files have been replaced, log in using the original (backed up) user name and password.

NOTE: Serial Relay Agents and System Agents do not need to restore any files upon reinstallation.

HP Rack and Power Manager User Guide

D-1