HP Power Proter Software, Rack and Power Manager Software manual Troubleshooting

Models: Power Proter Software Rack and Power Manager Software

1 181
Download 181 pages 43.79 Kb
Page 160
Image 160

Troubleshooting

Table 6-1: Troubleshooting continued

Symptom

Possible Cause

Suggested Action

When installing the software on a NetWare machine, the following error message displays: “UPS Communication Lost.”

The Serial Relay Agent fails to communicate with the UPS.

Verify that the serial cable is plugged into the correct communications port.

Be sure to use upper-case letters when entering the communications port, for example, COM2.

When upgrading the software on a NetWare machine, the following error message displays: “Failed binding a network handle to the NetXCP port.”

Old modules are left from a previous version.

Unload the modules SRA.NLM and SHDNAGNT.NLM and retry the upgrade.

Color palettes are managed

The system is configured

Increase the monitor resolution to

improperly.

to only display 256 colors.

display more than 256 colors when

 

 

browsing into HP Rack and Power

 

 

Manager.

 

 

 

Not all devices and agents in

The timeout and retries

Increase these values on the

your enterprise are

values are too low.

Automatic Discovery screen and

discovered.

 

the Manual Discovery screen.

 

 

 

 

The wrong IP address or

Verify the IP addresses and IP

 

IP address range is used.

address ranges on the Automatic

 

 

Discovery screen and the Manual

 

 

Discovery screen.

 

 

 

 

An incorrect Community

Verify that the discovery is

 

String is being used.

configured to use the correct

 

 

Community Strings.

 

 

 

 

There is no System Agent

Verify that the System Agent is

 

installed.

installed and the service is running.

 

 

 

CMC sensors are disabled in

The sensor is not

Install the sensor.

the Current Status window of

installed.

 

the CMC Device Overview

 

 

screen.

 

 

 

 

 

 

The sensor is not

Enable the sensor on the Sensor

 

enabled.

Setup screen.

 

 

 

The CMC door-locking feature

The intrusion sensors are

Assign at least one intrusion

is not working properly.

not properly assigned.

sensor to each lockset.

 

 

 

Device actions are not working

The normal, opposite

Configure the normal, opposite

properly.

response to the initial

response to each event on the

 

event response is not

Device Actions tab of the Event

 

configured.

Response screen.

 

 

 

Connection to a device is lost.

HP Rack and Power

Verify the computer interface cable

 

Manager lost

connection.

 

communication with the

 

 

UPS.

 

 

 

 

 

 

continued

6-2

HP Rack and Power Manager User Guide

Page 160
Image 160
HP Power Proter Software, Rack and Power Manager Software manual Troubleshooting