C

Using HP Rack and Power Manager with HP Insight Manager 7 SP2

HP Rack and Power Manager software can be configured to send alert traps to HP Insight Manager 7, as well as other SNMP management applications. To send event alert traps to Insight Manager 7:

Configure Insight Manager 7 to receive a trap from HP Rack and Power Manager.

Configure HP Rack and Power Manager to send the appropriate event alert traps.

Configuring Insight Manager 7 SP2

Verify that the HP Rack and Power Manager MIB (CPQRPM.MIB) is registered in Insight Manager 7:

1.Upload the HP Rack and Power Manager MIB. The HP Rack and Power Manager MIB (CPQRPM.MIB) can be found on the HP Management CD and in the MIB folder of the HP Rack and Power Management CD.

2.Register the Rack and Power MIB.

NOTE: For additional information on uploading and registering a MIB in Insight Manager 7, refer to the HP Insight Manager Technical Reference Guide located on the HP Management CD.

Configuring HP Rack and Power Manager

To configure HP Rack and Power Manager to send traps to Insight Manager 7:

1.Add the Insight Manager 7 server as an SNMP Trap recipient. For information on configuring SNMP Trap recipients, refer to “Notification Recipients Screen” in Chapter 4 of this guide.

2.Configure HP Rack and Power Manager to send alert notifications to Insight Manager 7 as SNMP traps. For more information on configuring alert notifications, refer to “Event Response Overview Screen” in Chapter 5 of this guide.

HP Rack and Power Manager User Guide

C-1