Overview
Configuration F
Figure 1-7 illustrates a redundant configuration in which servers with dual power supplies are protected by multiple UPSs. One server is serially attached to a UPS. The first server and a second UPS are connected directly to the network. One server power supply is connected to a receptacle on the rear panel of each UPS. Each UPS is connected to a separate power feed. The UPSs are monitored by a Management Server located elsewhere on the network.
IMPORTANT: When planning a redundant configuration, consider that in normal operating conditions, servers with multiple power supplies equally distribute the power load across each power feed. A server with two power supplies applies 50% of the load to each power feed. In the event that one power feed fails, the second power feed must be able to handle 100% of the load. Ensure that each UPS in the redundant configuration can support the entire load in the event of a power failure.
Redundant UPS configurations should be tested thoroughly to ensure the load handling capabilities and power fail settings of each UPS before an actual power failure event.