Operation
Restart Settings Box
The Restart Settings box contains information about the restart for UPS load segments. After shutdown occurs, the Management Server restarts affected devices according to these settings. Each load segment is displayed.
To configure the restart timings:
1.Select the load segment you want to configure by clicking its name in the top left corner of the box.
NOTE: If no load segment is selected, the information at the bottom of the box is not displayed.
2.Enter the number of minutes that should elapse from the time of the power restoration to the beginning of the load segment restart. The maximum delay that can be entered is 60 minutes.
3.Click Submit to save the changes, click Cancel to reject all changes and keep the box open, or click View Shutdown Settings to display the Shutdown Settings box.
HP Rack and Power Manager User Guide |