Chapter 2 Preparing for Installation
Environmental Monitoring and Reporting Overview for the Cisco 7500 Series
In the following example, all current measured values fall within the Normal status range. The first voltage parameter in the table, +12(V), shows that the Normal range for the +12V sense spans 10.20V through 13.80V. The current measured value, 12.05V, falls within that range and is therefore displayed in the Normal column.
Router# show env table
Environmental Statistics
Environmental status as of Wed
Data is 46 second(s) old, refresh in 14 second(s)
WARNING: Fan has reached CRITICAL level |
| |||
Voltage Parameters: |
|
|
| |
SENSE | CRITICAL |
| NORMAL | CRITICAL |
+12(V) |
| 10.20 | 12.05(V) | 13.80 |
+5(V) |
| 4.74 | 4.96(V) | 5.26 |
| ||||
+24(V) |
| 20.00 | 23.80(V) | 28.00 |
Temperature Parameters: |
|
|
|
| |
SENSE | WARNING | NORMAL |
| WARNING | CRITICAL SHUTDOWN |
Inlet | 10 | 32(C) | 39 | 46 | 64 |
10 | 40(C) | 70 | 77 | 88 |
The following example shows only the Temperature Parameters section of the table. In this example, the measured value at the inlet sensor is 41°C, which falls within the warning range (39°C through 46°C) and is therefore displayed in the Warning column.
Temperature Parameters:
SENSE | WARNING |
| NORMAL |
| WARNING |
| CRITICAL SHUTDOWN |
Inlet |
| 10 |
| 39 | 41(C) | 46 | 64 |
| 10 | 40(C) | 70 |
| 77 | 88 |
In the Cisco 7505, the show environment all command displays an extended report that includes all the information in the show environment command display, plus the power supply status, the number of intermittent power failures (if any) since the system was last powered on, and the measured values at the temperature sensors and the DC lines. The refresh time indicates that the parameters will be measured again in 29 seconds; any changes to a measurement will not be reflected in the display until at least 40 seconds have elapsed and the current information is refreshed.
Router# show env all
Environmental Statistics
Environmental status as of Wed
Data is 31 second(s) old, refresh in 29 second(s)
WARNING: Fan has reached CRITICAL level
Power Supply: 600W AC (or 600W DC)
No Intermittent Powerfails
+12 volts measured at 12.00(V)
+5 volts measured at 5.02(V)
| Cisco 7500 Series Installation and Configuration Guide |