Installing the Control Unit

 

TYPICL AC GROUNDING

From AC

 

Load Center

 

(2 separately

 

fused 15 A

Ground

circuits)

(#14 AWG)

 

 

4" Box (RACO 230

 

or equivalent)

HUBBELL Receptacles

 

(5262 15 A

 

or equivalent)

 

Single-Point

Ground

 

Ground Bar

4" Cover

(RACO 807

Mounted on a 4" Box

or equivalent)

(Square "D" PK9GTA or

Approved

approved equivalent)

 

Building Ground

 

(#6 AWG Copper)

#12 or #14 AWG Copper Wire to EAch Power Supply Grounding Screw

Figure 2-1. AC Grounding Requirements

Each carrier requires one outlet receptacle.

Additional AC outlets may be required for auxiliary equipment.

If a printer or a PC is to be installed with the system, it must be plugged into the same AC branch as the power supply of the basic carrier.

If the printer or PC is 50 ft (15 m) or more from the control unit or is plugged into a different AC circuit, asynchronous data units (ADUs) must be installed as well. Complete installation instructions are provided in Chapter 5.

Power and Grounding 2-7