Installing the Control Unit

Grounding Requirements

Proper grounding of the installation site safeguards system functioning by protecting the system from the following:

lightning

power surges

power crosses on central office trunks

electrostatic discharge (ESD)

When installing the control unit, make sure that you meet the following grounding requirements:

The control unit, the central office trunk protector, and the AC power service panel should be as close to each other as possible.

Because equipment can be located throughout a building, the National Electrical Code requires that the ground point for the central office trunk protector be bonded to the AC power ground as shown in Figure 2-3.

The AC outlet and the single-point ground bar must be properly grounded as shown earlier in Figure 2-1.

Each power supply in the control unit must be connected to the single-point ground bar by a #12 AWG or a #14 AWG solid copper wire. Figures 2-1and 2-3 show this connection.

This wire run should be as short as possible, preferably within 5 ft

(152 cm), not to exceed 10 ft (305 cm). This procedure is described later in this chapter under “Providing the Proper Grounding.”

The AC outlet must be connected to the 147A protector with #12 AWG or a #14 AWG solid copper wire.

Power and Grounding

2-11

Page 50
Image 50
AT&T Release 2.0 manual Grounding Requirements