Installing and Cabling the Cabinets

Connect Cabinet Grounds and Other Grounds

The following additional grounding requirements must be met:

The approved ground wire must be green, 6 AWG (#40) (16 mm2), copper, stranded wire (this is in addition to the ground wire in the AC power cord)

Bond all approved grounds at the single-point ground to form a single grounding electrode system

Install the Ground Block

To install the ground block

1.Mount the ground block as shown in Figure 10.

2.Make the cable connections as shown in Figure 11.

Figure 10: Ground Block Installation to Right Panel

2

A

2

1

indmingb RPY 012398

Figure notes:

 

1. #12 x 1-inch shoulder screws

2. Single-point ground block