Task Table

3.Type neither in the Alarm Origination to OSS Numbers field and press Enter.

Note:

Disabling alarm origination prevents the system from generating alarms, thus preventing unnecessary trouble tickets.

For some DEFINITY ECS software versions, set the Cleared Alarm Notification and Restart Notification fields to disable before pressing Enter.

Check Link Status

To check link status:

1.Enter display communication-interface links and press Enter. Write down all enabled links

2.Type status link number and press Enter for each enabled link.

3.Write down which links are in service.

Save Translations

To save translations:

1.Type save translation and press Enter to write all translations from memory to the original translation flashcard, which takes about 10 minutes.

When the save translations is successful, the error code must be a zero; otherwise, the translations are not copied. If the translations were corrupted, the following error message displays when logging in:

! WARNING:

Translation corruption detected; call Avaya distributor immediately.

Note:

The save translation command cannot function if translations are corrupt. Refer to Translation Corruption Detected on page 358 to clear the problem.

Issue 10 June 2005 191

Page 191
Image 191