Strata CTX Configuration

Reserve Power (CTX100 and CTX670)

Determine CTX670 system miscellaneous power components in the following worksheet. (See Tables 2-63and 2-66for component descriptions.) These components are not used on CTX100 systems.

Enter the number of cabinet power components needed:

Main Location ____________ Remote Location 1___ 2___ 3___ 4____5___ 6____

CTX670 Cabinet Power

Enter the Number

Components

Required

Spare Power Supply

BPSU672

 

 

 

 

AC Power Strips

RPSB2

 

 

 

BPSB240

 

 

 

 

 

 

208/240VAC Power Supply Cord

BACL240

 

 

 

 

Battery Cables

PBTC-3M

 

 

 

BBTC1A-2.0M

 

 

 

 

 

 

Battery DIstribution Box

BBDB

 

 

 

 

Conduit Box

BCCB120

 

 

 

BCCB240

 

 

 

 

 

 

Floor Mount Stand

BFIF

 

 

 

 

Reserve Power (CTX100 and CTX670)

Two or four customer-supplied 12VDC reserve batteries (80 ampere-hours max.) can be connected to either system to maintain normal operation during a power failure (see Tables 2-61~2-64). The batteries are kept in a highly-charged state by the power supply’s battery charger and must be connected when the system is operating normally. Fully charged batteries must be connected when normal AC power is available, batteries cannot be connected after/during an actual power failure.

The battery changer is standard on the CTX670 power supply. An optional ABCS battery changer must be used in the CTX100 power supply.

Table 2-61 CTX100 Reserve Power Characteristics

Battery Charger Characteristics

Maximum Battery Charger Drain (-24VDC)

 

 

 

 

 

 

 

Charger: current limiting

Base Cabinet

 

3.15 amps

Nominal float voltage: 2.275 volts/cell

 

Charge current: 280mA amps maximum

Base + Expansion Cabinets

6.30 amps

Battery discharge cut-off voltage: 20.5 ±0.5VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 2-62 CTX100 Typical Reserve Power Duration Estimates1

 

 

 

 

 

 

 

 

 

 

 

Number of Cabinets

 

1

2

 

 

 

Estimated operation time Two-battery configuration

25 hr.

12.5 hr.

 

 

 

 

 

 

 

 

 

Estimated operation time Four-battery configuration

50 hr.

25 hr.

 

 

 

 

 

 

 

 

 

DC Current Drain (-24VDC)

 

3.15 amps.

6.30 amps.

 

 

 

 

 

 

 

 

1. Assumes 80 ampere-hours with 12VDC batteries.

2-48