Strata CTX Configuration

Primary/Reserve Power Cabinet Hardware

CTX670 Cabinet AC Power Component Requirements for Wall Mounted Systems

Tables 2-67and 2-68show the cabinet parts required to distribute AC power for various configurations of the Strata CTX cabinets.

Table 2-67 Wall Mount Cabinet Power Component Requirements for 120VAC Primary Power

Local Electrical Code

1 Cabinet

2 Cabinets

3 Cabinets

4 Cabinets

5 Cabinets

6 Cabinets

7 Cabinets

 

 

 

 

 

 

 

 

Allows only one

 

 

 

 

 

 

 

120VAC power cord

0 RPSB2

1 RPSB2

1 RPSB2

N/A

N/A

N/A

N/A

from system

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Allows two 120VAC

 

 

 

 

 

 

 

power cords from

0 RPSB2

0 RPSB2

1 RPSB2

1 RPSB2

2 RPSB2

N/A

N/A

system

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

One dedicated, isolated, 20 amp. AC circuit breaker with dual outlets is required.

N/A= If the system contains more than three cabinets and if the local code allows only one AC cord, the system requires a BCCB120 conduit box wired by a certified electrician when using 120VAC as primary power. Otherwise, 208VAC or 240VAC should be used as the primary power source (see cabinet power options listed below). If more than five cabinets are installed, 208VAC or 240VAC is required.

Table 2-68 Wall Mount Cabinet Power Component Requirements for 208VAC or 240VAC Primary Power

Local Electrical

1 Cabinet

2 Cabinets

3 Cabinets

4 Cabinets

5 Cabinets

6 Cabinets

7 Cabinets

Code

 

 

 

 

 

 

 

Allows One AC

 

1 BPSB240

1 BPSB240

2 BPSB240

2 BPSB240

3 BPSB240

3 BPSB240

power cord from

1 BACL240

2 BACL240

3 BACL240

4 BACL240

5 BACL240

6 BACL240

7 BACL240

system

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Important! The plugs and wall receptacles required by the local electrical code might differ for 208VAC and 240VAC. Thus in some areas of the U.S., the plug used on the Toshiba 240VAC power strip and 240VAC power supply cord (NEMA code 6-20P) can not be used for 208VAC installations. In this case, when using 208VAC, the AC plugs on the BPSB240 power strip cord that connects directly to the 208VAC wall outlet must be changed by a certified electrician per the local electrical code.