18 DCOM Settings with the dcomcnfg System Program
18.6.3“Identity” Tab
Description of the Settings
The settings made in the “Identity” tab specify the account to be accessed to check the permissions of the user of the object. Here, various settings are possible:
S“Interactive User”
S“The Launching User”
S“This User”
Table
Setting | Meaning |
|
|
“Interactive User” | The account of the currently logged on user is used. |
| If, however, no user uses the computer, there is no interactive user |
| and the COM object cannot be created. If you operate without a |
| logged on user, use the “ThisUser” setting. “Interactive user” is the |
| default setting for the OPC Server for SIMATIC NET. |
|
|
“The Launching User” | The account of the user that launched the OPC client is used. |
| This user must then also have the required permissions; in other |
| words, must be entered in the “Security” tab. The user must also |
| have the default permissions entered for the group of users on this |
| computer; in other words, must belong to the group of users. |
| This mode must not be used with the OPC server for SIMATIC NET, |
| since the OPC server would otherwise be started more than once by |
| different user accounts and this is not permitted. |
|
|
“This User” | The account of a specified user is used. This user must have the |
| required permissions; in other words, must be entered in the |
| “Security” tab. The user must also have the default permissions |
| entered for the group of users on this computer; in other words, must |
| belong to the group of users. |
| This setting must be used to operate the OPC server for SIMATIC |
| NET (logged on users). |
| S Multiterminal Mode |
| You should also use the setting described here “This user” for |
| multiterminal mode on the PC station. |
|
|
Commissioning PC Stations - Manual and Quick Start | 265 |
Release 5/2005 |