B Description of the PROFINET Configuration File

The Timeout Parameter

This parameter is specified in section [<connectionname>].

The connection name contains the IP address from the iMap project engineering (network view) and the PROFInet device name configured in iMap.

Parameter

Meaning

 

 

Syntax

[192.11.2.34S7-300 Station (1)]

 

Timeout = 15000

 

 

Purpose

The “Timeout” parameter is an error monitoring

 

time. If a pending job cannot be processed within

 

this monitoring time, the job is acknowledged with

 

an error.

 

 

Default

15000

 

 

Possible Values

milliseconds

 

 

The QualityOfStateValue Parameter

This parameter is specified in section [<connectionname>].

The connection name contains the IP address from the iMap project engineering (network view) and the PROFInet device name configured in iMap.

Parameter

Meaning

 

 

Syntax

[192.11.2.34S7-300 Station (1)]

 

QualityOfStateValue = 100

 

 

Purpose

The required QualityofServiceValue is used to

 

restrict the frequency of transmission of data on a

 

partner device. It describes the required update

 

quality of the data. Process value on the partner

 

device are updated at this sampling rate.

 

 

Default

100 (the cycle time of the PROFInet OPC Server)

 

 

Possible Values

milliseconds

 

 

Commissioning PC Stations - Manual and Quick Start

291

Release 5/2005

C79000- G8976- C156 - 07

Page 291
Image 291
Siemens C79000-G8976-C156-07 quick start Timeout Parameter, QualityOfStateValue Parameter