6Using the CP 1616 as a PROFINET IO Controller/Device
6.1Initialize CP 1616 (IP address and device name)
Assigning the IP address
1.
2.
3.
4.
5.
Follow the steps outlined below
Open the SIMATIC Manager.
Select the menu command PLC " Ethernet " Assign Ethernet Address...
The “Assign Ethernet Address” menu opens.
Click on “Browse” in the “Select station to initialize” area and select the CP 1616.
In the “Set IP configuration” area, set the IP address of the CP 1616 and the subnet mask and click “Assign IP Configuration”.
The IP address entered here must match the configured address.
In the “Assign device name” area, enter the device name of the CP 1616 and click “Assign Name”.
The device name entered here must match the configured device name because when the CP 1616 is configured as a device, only the device name is relevant (not the IP address).
Note
If the CP 1616 was configured previously as a controller, you must first run a complete memory reset before the device name can be changed.
Following every memory reset, the CP must be restarted (by STEP 7) otherwise operation as a device is not possible!
Commissioning PC Stations - Manual and Quick Start | 71 |
Release 5/2005 |