4.7General Requirements
1.The safety standards for Information Technology Equipment are only valid if the building installation conforms to the National Electrical Code for the country where the equipment is being installed.
2.For equipment that has a pluggable connection to its power source, the power source outlet socket must be located near the equipment and must be easily accessible.
3.For protection against electric shock, certain parts of this equipment, including the interface connections have been designed so that the voltage is limited to a safe value. In order to maintain this protection it is essential that any equipment connected to Fujitsu products shall have interface connections which are similarly protected.
4.When installing and disassembling equipment, be sure to follow
The following are general electrical supply requirements:
a.Line noise limitations must not exceed 1250V with a maximum 1∝s duration, and the repetition rate not to exceed 100Hz
b.Socket outlets must provide protective earth grounding and be of a polarized type
c.Before installing the terminal, check the power lines for loads that could cause large variations in voltage. Electrical devices that use a great deal of power such as air conditioners, elevators, copying machines, and large motors can cause large drops in voltage. When severe electrical interference occurs, installing radio frequency (RF) filters, or an isolation transformer, or both may be necessary. If voltage surges caused by lightning are likely to occur, install an arrester.
d.Fujitsu supplied cables should be used to connect the system to the power supply outlet but, where this is not possible, the minimum requirement for the mains cables is as follows: For connection to
e.This ITE (Information Technology Equipment) power supply is designed for use on a power system with an earthed neutral, i.e., a TN or TT power