Chapter 4 Explanation of Functions

4.2.35 Carrier frequency setting

The carrier frequency setting function (b083) allows you to change the carrier frequency of the PWM waveform output from the inverter.

Increasing the carrier frequency can lower the metallic noise from the motor, but may increase the inverter noise and current leakage.

You can use this function effectively to avoid resonance of the mechanical system and motor.

Item

Function code

Range of data

Description

Carrier frequency

b083

0.5 to 15.0 (kHz) (*1)

 

setting

 

 

 

 

*1 The maximum carrier frequency varies depending on the inverter capacity.

When increasing the carrier frequency (fc), derate the output current as shown in the following table: Derated output current is to be set as electronic thermal protection level (4.2.29).

Derating is not needed when electronic thermal level is already set to lower then derating level.

Voltage

 

200 V class

 

400 V class

class

 

 

 

 

 

 

 

Inverter

Maximum

 

Derating at fc=15 kHz

Maximum

Derating at fc=15 kHz

capacity

fc (kHz)

 

 

fc (kHz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15kW

12

 

95% (60.8 A or less)

14

95% (30.4A or less)

18.5kW

10

 

90% (68.4A or less)

10

90% (34.2A or less)

22kW

7

 

70% (66.5A or less)

6

75% (36.0A or less)

30kW

5

 

80% (96.8A or less)

10

75% (43.5A or less)

37kW

10

 

75% (108.7A or less)

8

80% (60.0A or less)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200 V class

 

 

 

 

 

 

400 V class

 

 

 

37kW

30kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

current

100

 

 

 

 

 

 

15kW

current

100

 

 

 

 

 

 

15kW

 

 

 

 

 

 

 

 

 

 

 

 

 

90

 

 

 

 

 

 

90

 

 

 

 

 

 

18.5kW

 

 

 

 

 

 

18.5kW

 

 

 

 

 

 

 

95

 

 

 

 

 

 

 

 

95

 

 

 

 

 

 

 

output

85

 

 

 

 

 

 

 

output

85

 

 

 

22kW

 

 

80

 

 

 

 

 

 

30kW

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of

75

 

 

 

 

 

 

37kW

of

75

 

 

 

 

 

 

 

70

 

 

 

 

 

 

22kW

70

 

 

 

 

 

 

 

Derating

 

 

 

 

 

 

Derating

 

 

 

 

 

 

 

65

 

 

 

 

 

 

 

65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

55

2

4

6

8

10

12

14 15

 

55

2

4

6

8

10

12

14 15

 

0.5

 

0.5

 

 

 

Carrier frequency (kHz)

 

 

 

 

Carrier frequency (kHz)

 

If you use the inverter with settings that exceed the rated maximum carrier frequency or derated output current (with a maximum carrier frequency of 15 kHz), the inverter may be damaged or its life may be shortened.

4 - 43