Chapter 4 Explanation of Functions
4.3.16 Zero-return function (ORG, ORL)
- One of three types of zero-return operations can be selected by zero-return mode selection (P068). When a zero-return operation ends, the current position counter is cleared (to 0).
- Use zero-return direction selection (P069) to select the direction of zero-return operation.
- If zero-return operation is not performed, position control is performed based on the assumption that the motor position detected at power-on is the origin.
<1> Low-speedzero-return

ON

(2)

Low-speed zero-return speed (P070)

(3)

OriginPosition

(1)The inverter accelerates the motor for the specified acceleration time to the low-speed zero-return speed.

(2)The inverter runs the motor at the low-speed zero-return speed.

(3)The inverter performs positioning when the ORL signal is input.

ON

ON

(2)High-speed zero-return

speed (P071)

(3)

Origin

Position

(5)(4)

Low-speed zero-return speed (P070)

<1> The inverter accelerates the motor for the specified acceleration time to the high-speed zero-return speed.

<2> The inverter runs the motor at the high-speed zero-return speed.

<3> The inverter starts deceleration when the ORL signal is turned on. <4> The inverter runs the motor in the reverse direction at the low-speed zero-return speed.

<5> The inverter performs positioning when the ORL signal is turned off.

 

 

 

 

 

 

 

 

 

 

 

<1> The inverter accelerates the

ORG terminal

 

 

 

 

 

 

 

 

 

motor for the specified acceleration

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

time to the high-speed zero-return

ORL terminal

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

speed.

 

 

 

 

 

 

 

 

 

 

 

Output frequency

(2)

 

 

 

 

 

 

<2> The inverter runs the motor at the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(3) Low-speed zero-return speed

high-speed zero-return speed.

 

 

 

(1)

 

 

<3> The inverter starts deceleration

 

 

 

 

 

 

 

 

(P070)

when the ORL signal is turned on.

 

 

 

(6)

(7)

 

<4> The inverter runs the motor in the

 

 

 

 

 

 

 

Origin Position

reverse direction at the low-speed

 

 

 

(5)

zero-return speed.

 

 

 

(4)

 

 

 

 

 

 

 

 

 

 

high-speed zero-return speed

<5> The inverter starts deceleration

 

 

 

 

 

 

 

 

 

(P071)

when the ORL signal is turned off.

Z pulse

 

 

 

 

 

 

 

 

<6> The inverter runs the motor in the

 

 

 

 

 

 

 

 

forward direction at the low-speed

 

 

 

 

 

 

 

 

 

 

 

zero-return speed.

<7> The inverter performs positioning at the first Z pulse position after the ORL signal is turned on.

4 - 109