Related code
C001 to C008: Terminal [1] to [8] functions
Related code
C001 to C008: Terminal [1] to [8] functions
Chapter 4 Explanation of Functions

4.2.52 External trip (EXT) function

The external trip function allows you to make the inverter trip according to the error (trip) signal generated by an external system.

To use this function, assign function "12" (EXT) to one of the terminal [1] to [8] functions (C001 to C008). When the EXT terminal is turned on, the inverter trips with error code "E12" displayed and stops the output.

After the inverter trips with error code "E12" displayed, it will not be recovered from tripping, even when the error signal from the external system is reset (i.e., the EXT terminal is turned off).

To recover the inverter from tripping, reset the inverter or turn the inverter power off and on.

Item

Function code

Data

Description

Terminal [1] to [8] functions

C001 to C008

12

EXT: External trip

Note: Do not turn on the EXT terminal after the inverter power is shut off. Otherwise, the error history may not be stored correctly.

Operation commands

FW and RV

EXT terminal

Motor speed

 

Free running

 

 

 

 

RS terminal

Alarm output terminal

4.2.53 3-wire interface operation function (STA, STP, and F/R)

The 3-wire interface operation function allows you to use automatic- reset contacts (e.g., pushbutton switches) to start and stop the inverter.

Specify "01" (control circuit terminal block) for the run command source setting (A002).

Assign function "20" (STA), "21" (STP), and "22" (F/R) to three of the terminal [1] to [8] functions (C001 to C008) to enable the control operations described below. Assigning the STP function to an intelligent input terminal disables the functions of the FW and RV terminals.

The figure below shows the inverter outputs according to terminal operations.

Item

Function code

Data

 

 

Description

 

 

 

 

 

20

 

STA: Starting the motor

Terminal [1] to [8] functions

C001 to C008

21

 

STP: Stopping the motor

22

 

F/R: Switching the motor operation

 

 

 

 

 

 

 

 

 

 

 

 

direction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STA

 

 

ON

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STP

 

 

ON

 

OFF

 

 

 

 

 

 

 

 

 

 

F/R

Output frequency

Forward rotation

Reverse rotation

4 - 57

Page 115
Image 115
Hitachi SJ700-2 instruction manual External trip EXT function, 53 3-wire interface operation function STA, STP, and F/R