Chapter 4 Explanation of Functions

Connection

As illustrated below, connect the inverters in parallel to the external control system, and connect the RP and SN terminals with a jumper on the inverter at the end of the network. (Similarly jumper the RP and SN terminals when only one inverter is connected to the external control system for RS485 communication.) Connecting the RP and SN terminals enables the terminating resistor in the control circuit terminal block board of the inverter, which suppresses signal reflections.

External control

system

 

 

SP SN RP SN

SP SN RP SN

SP SN RP SN

(2) Required settings

The following table lists the inverter settings required for the RS485 communication:

Item

Function code

Data or range of data

Description

 

 

02

Loopback test

Communication speed

C071

03

2,400 bps

04

4,800 bps

selection

 

05

9,600 bps

 

 

 

 

06

19,200 bps

 

 

 

Assignment of a station number to the

 

 

 

inverter

Node allocation

C072

1. to 32.

(Set this item when your inverter is

 

 

 

connected together with other(s) to a

 

 

 

control system.)

Communication data length

C073

7

7 bits

selection

8

8 bits

 

Communication parity

C074

00

No parity

01

Even parity

selection

 

02

Odd parity

 

 

Communication stop bit

C075

1

1 bit

selection

2

2 bits

 

 

 

00

Tripping

 

 

01

Tripping after decelerating and stopping

Selection of operation after

C076

the motor

 

communication error

02

Ignoring the errors

 

 

 

03

Stopping the motor after free-running

 

 

04

Decelerating and stopping the motor

Communication trip limit time

C077

0.00 to 99.99 (s)

Limit length of time to determine

setting

communication train disconnection

 

 

Communication wait time

C078

0. to 1000. (ms)

Time to wait until the inverter returns a

 

response

 

 

 

Communication mode

C079

00

ASCII mode

selection

01

Modbus-RTU mode

 

4 - 114