Chapter 4 Explanation of Functions

Register

Function name

Function

R/W

Monitoring and setting items

Data

No.

code

resolution

 

 

 

003Ah

Trip monitoring 5 (factor)

 

 

See the list of inverter trip factors below

-

003Bh

Trip monitoring 5 (inverter status)

 

 

See the list of inverter trip factors below

-

003Ch

Trip monitoring 5 (frequency) (high)

 

 

0 to 40000

0.01 [Hz]

003Dh

Trip monitoring 5 (frequency (low)

 

 

 

 

 

 

003Eh

Trip monitoring 5 (current)

d085

R

Output current at tripping

0.1 A

003Fh

Trip monitoring 5 (voltage)

DC input voltage at tripping

1 V

 

 

0040h

Trip monitoring 5 (running time) (high)

 

 

Cumulative running time at tripping

1h

0041h

Trip monitoring 5 (running time) (low)

 

 

 

 

 

 

0042h

Trip monitoring 5 (power-on time) (high)

 

 

Cumulative power-on time at tripping

1h

0043h

Trip monitoring 5 (power-on time) (low)

 

 

 

 

 

 

0044h

Trip monitoring 6 (factor)

 

 

See the list of inverter trip factors below

-

0045h

Trip monitoring 6 (inverter status)

 

 

See the list of inverter trip factors below

-

0046h

Trip monitoring 6 (frequency) (high)

 

 

0 to 40000

0.01 [Hz]

0047h

Trip monitoring 6 (frequency (low)

 

 

 

 

 

 

0048h

Trip monitoring 6 (current)

d086

R

Output current at tripping

0.1 A

0049h

Trip monitoring 6 (voltage)

DC input voltage at tripping

1 V

 

 

004Ah

Trip monitoring 6 (running time) (high)

 

 

Cumulative running time at tripping

1h

004Bh

Trip monitoring 6 (running time) (low)

 

 

 

 

 

 

004Ch

Trip monitoring 6 (power-on time) (high)

 

 

Cumulative power-on time at tripping

1h

004Dh

Trip monitoring 6 (power-on time) (low)

 

 

 

 

 

 

004Eh

Programming error monitoring

d090

R

Warning code

-

004Fh to

Unused

-

-

Inaccessible

-

08FFh

 

 

 

 

0000: Motor constant recalculation

 

0900h

Writing to EEPROM

-

W

0001: Set data storage in EEPROM

-

Other: Motor constant recalculation and set data

 

 

 

 

 

 

 

 

 

storage in EEPROM

 

0901h to

Unused

-

-

Inaccessible

-

1000h

 

 

 

 

 

Note 1: Assume that the rated current of the inverter is "1000".

Note 2: If a number not less than "1000" (100.0 seconds) is specified, the second value after the decimal point will be ignored.