Chapter 4 Explanation of Functions

(3) Internal DC braking (A051: 01)

You can apply DC braking to the motor even without entering braking signals via the DB terminal when the inverter starts and stops. To use the internal DC braking function, specify "01" for the DC braking enable (A051).

Use function "A057" to set the DC braking force for starting, and use function "A058" to specify the DC braking time for starting, regardless of the braking mode selection (edge or level mode). (See examples 4-a and 4-b.)

Set the braking force for periods other than starting by using the DC braking force setting (A054).

Set the output frequency at which to start DC braking by using the DC braking frequency setting (A052). When you set the DC braking wait time (A053), the inverter output will be shut off when the output frequency reaches the setting of "A052" after the operation command (FW signal) is turned off, and the motor will run freely for the delay time set by "A053". DC braking will be started after the delay (A053). The internal DC braking operation to be performed when the operation command is switched from the stop command to the start command varies depending on the braking mode (edge or level mode).

Edge mode: The DC braking time setting (A055) is given priority over operation commands, and the inverter performs DC braking according to the setting of "A055". When the output frequency reaches the setting of "A052" the inverter performs DC braking for the time set for "A055". Even if the stop command is input during DC braking, DC braking continues until the time set for "A055" elapses. (See examples 5-a and 6-a.)

Level mode: Operation commands are given priority over the DC braking time setting. The inverter follows operation commands, regardless of the DC braking time setting (A055). If the start command is input during DC braking, the inverter starts the normal motor operation, regardless of the DC braking time setting (A055). (See examples 5-b and 6-b.)

(a) Edge mode

 

(b) Level mode

 

i) (Example 4-a) when the start command is input:

i) (Example 4-b) when the start command is input:

FW

 

 

FW

 

 

Output

 

 

Output

 

 

frequency

 

 

frequency

 

 

A057

 

 

 

A057

 

 

A058

 

A058

 

ii) (Example 5-a) when the stop command is input:

ii) (Example 5-b) when the stop command is input:

FW

 

 

FW

 

 

Output

 

Free running

Output

Free running

 

 

 

 

frequency

 

 

frequency

 

 

A052

A053

A055

 

A053

A055

 

 

 

 

 

 

A052

 

 

 

 

 

 

ii) (Example 6-a) when the stop command is input:

ii) (Example 6-b) when the stop command is input:

FW

FW

Output

Output

frequency

frequency

A055

A055

A052

A052

4 - 22

Page 80
Image 80
Hitachi SJ700-2 Ii Example 5-a when the stop command is input, Ii Example 6-a when the stop command is input