Hitachi SJ700-2 instruction manual Frequency operation function, +fO2 + fO2

Models: SJ700-2

1 274
Download 274 pages 15.86 Kb
Page 71
Image 71
Related code
A141: Operation-target frequency selection 1
A142: Operation-target frequency selection 2
A143: Operator selection
A001: Frequency source setting
A076: PV source setting

Chapter 4 Explanation of Functions

(Example 1) When the motor operation is not reversible

FW

AT

Main frequency command via the OI or O terminal

0

(Example 1) When the motor operation is reversible

 

 

 

 

 

FW

 

 

 

 

 

 

 

 

 

AT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fOI

fO

 

Main frequency

 

fOI

fO

 

 

 

 

 

command via the OI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or O terminal

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

fO2

 

Auxiliary

 

 

 

 

 

 

 

 

 

Auxiliary

 

frequency

0

 

 

 

 

 

 

 

 

frequency

0

 

 

 

 

 

 

 

command via

 

 

 

 

 

 

 

 

 

command via

 

the O2 terminal

 

 

 

 

 

 

 

 

 

the O2 terminal

 

fO + fO2

 

fOI

+fO2

fO

+ fO2

 

Actual frequency

Forward

 

Actual frequency

 

Forward

command

operation

 

command

 

 

operation

 

 

 

 

 

0

 

 

 

 

0

Reverse

 

 

 

 

 

 

 

 

 

 

 

 

operation

fO2

fOI +fO2

4.2.12 Frequency operation function

The frequency operation function allows you to use the result of an arithmetic operation on two frequency commands as the actual frequency command or PID feedback data.

To use the operation result as the actual frequency command, specify "10" for the frequency source setting (A001).

To use the operation result as the PID feedback data, specify "10" for the PV source setting (A076).

Item

Function code

Data

Description

 

 

00

Digital operator (A020/A220/A320)

 

 

(01)

Control on the digital operator

 

 

(Valid only when the OPE-SR is connected)

 

 

 

Operation-target frequency

A141/A142

02

Input via the O terminal

03

Input via the OI terminal

selection 1 and 2

 

04

Input via the RS485 terminal

 

 

 

 

05

Input from option board 1

 

 

06

Input from option board 2

 

 

07

Input of pulse train

Operator selection for

A143

00

Addition: (A141) + (A142)

01

Subtraction: (A141) - (A142)

frequency operation

 

02

Multiplication: (A141) x (A142)

 

 

Frequency source setting

A001

10

Output of operation result

PV source setting

A076

10

Output of operation result

Note 1: The [1] (up) and [2] (down) keys of the digital operator are ineffective when the frequency operation function is enabled. Also, the frequency displayed by the output frequency monitoring (d001), Scaled output frequency monitoring (d007), or output frequency setting (F001) cannot be changed with key operations.

Note 2: The settings of "A141" and "A142" can be the same.

4 - 13