Related code
C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function
C077: Communication trip time
Related code
C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function

Chapter 4 Explanation of Functions

Item

Function code

Data or range of data

Description

 

 

33

LOG1: Logical operation result 1

 

 

(C142, C143, and C144)

 

 

 

Terminal function

 

34

LOG2: Logical operation result 2

 

(C145, C146, and C147)

 

 

 

 

C021 to C025

35

LOG3: Logical operation result 3

 

(C148, C149, and C150)

 

 

 

C026

36

LOG4: Logical operation result 4

 

 

(C151, C152, and C153)

Alarm relay

 

 

 

37

LOG5: Logical operation result 5

terminal function

 

(C154, C155, and C156)

 

 

 

 

38

LOG6: Logical operation result 6

 

 

(C157, C158, and C159)

 

 

 

Logical output

C142/C145/C148/

Selection of "00" to "56" from the

Selection of operation-target 1

data (except LOG1 to LOG6) output

 

signal selection 1

C151/C154/C157

 

to intelligent output terminals

 

 

 

 

Logical output

C143/C146/C149/

Selection of "00" to "56" from the

Selection of operation-target 2

data (except LOG1 to LOG6) output

 

signal selection 2

C152/C155/C158

 

to intelligent output terminals

 

 

 

 

Logical output

C144/C147/C150/

00

AND

signal operator

01

OR

C153/C156/C159

selection

 

 

02

XOR

 

4.2.67 Capacitor life warning signal (WAC)

The inverter checks the operating life of the capacitors on the internal circuit boards on the basis of the internal temperature and cumulative power-on time.

You can monitor the state of the capacitor life warning (WAC) signal by using the life-check monitoring function (d022).

If the WAC signal is output, you are recommended to replace the main circuit and logic circuit boards.

Item

Function code

Data or range of data

Description

Terminal function

C021 to C025

39

WAC: Capacitor life warning signal

Alarm relay terminal function

C026

(for on-board capacitors)

 

4.2.68 Communication line disconnection signal (NDc)

This signal function is enabled only when ModBus-RTU has been selected for the RS485 communication.

If a reception timeout occurs, the inverter continues to output the communication line disconnection signal until it receives the next data.

Specify the limit time for reception timeout by setting the communication trip time (C077). For details, see Section 4.4, "Communication Functions."

External control equipment

Inverter

Monitoring timer

Communication trip time

Communication line disconnection signal (NDc)

(C077)

Item

Function code

Data or range of data

Description

Terminal function

C021 to C025

32

NDc: Communication line

Alarm relay terminal function

C026

disconnection signal

 

Communication trip time

C077

0.00 to 99.99 (s)

Setting of the limit time for

reception timeout

 

 

 

4 - 67

Page 125
Image 125
Hitachi SJ700-2 instruction manual Capacitor life warning signal WAC, Communication line disconnection signal NDc