Chapter 4 Explanation of Functions

4.2.95 Motor constants selection

Adjust the motor constant settings to the motor to be driven by the inverter.

When using a single inverter to drive multiple motors in the control mode based on VC, VP, or free V/f characteristic, calculate the total capacity of the motors, and specify a value close to the total capacity for the motor capacity selection (H003/H203).

When the automatic torque boost function is used, the motor constant settings that do not match the motor may result in a reduced motor or unstable motor operation.

You can select the motor constants that are used when the control mode is the sensorless vector control, 0Hz-range sensorless vector control, or vector control with sensor from the following three types:

(1)Motor constants of Hitachi general-purpose motor

(2)Motor constants tuned by offline auto-tuning

(3)Arbitrarily set motor constants

The motor constants set for the 1st motor control apply to the 3rd motor control.

Item

Function code

Data or range of data

Description

 

 

00

Constant torque characteristic (VC)

 

 

01

Reduced-torque characteristic (1.7th power

V/F characteristic

A044/A244/

of VP)

 

02 (*1)

Free V/f characteristic

curve selection

A344

03 (*1)

Sensorless vector control (SLV)

 

 

 

 

04 (*1)

0 Hz-range sensorless vector control

 

 

05 (*1)

Vector control with sensor (V2)

Motor data

H002/H202

00

Hitachi general-purpose motor constants

01

Motor constants tuned by auto-tuning

selection

 

02

Motor constants tuned by online auto-tuning

 

 

Motor capacity

H003/H203

0.2 to 75.0 (kW)

 

Motor poles setting

H004/H204

2, 4, 6, 8, or 10 (poles)

 

Motor constant R1

H020/H220

0.000 to 65.53 (Ω)

(*2)

Motor constant R2

H021/H221

0.000 to 65.53 (kgm2)

(*2)

Motor constant L

H022/H222

0.00 to 655.3 (mH)

 

Motor constant Io

H023/H223

0.00 to 655.3 (A)

(*2)

Motor constant J

H024/H224

0.001 to 9999. (kgm2)

(*3)

Auto constant R1

H030/H230

0.000 to 65.53 (Ω)

 

Auto constant R2

H031/H231

0.000 to 65.53 (Ω)

 

Auto constant L

H032/H232

0.00 to 655.3 (mH)

 

Auto constant Io

H033/H233

0.00 to 655.3 (A)

 

Auto constant J

H034/H234

0.001 to 9999. (kgm2)

 

*1

Any of "00" to "05" can be selected for the 1st motor (A044). Only "00" to "04" can be selected for the

 

2nd motor (A244). Only "00" or "01" can be selected for the 3rd motor (A344).

*2

If you copy the data from a J300 series inverter to your SJ700 series inverter, set constants R1, R2,

 

and Io as follows:

 

R1SJ700 = R1J300/1.125 R2SJ700 = R2J300/1.2 Io = V/{272 x (2 x MJ300 + LJ300) x 10-3}

 

V: Voltage class (200 or 400 V)

*3

Convert the moment of inertia (J) into the motor shaft data. When the value of J is large, the motor

 

response is fast, and the motor torque increases quickly. When the value of J is small, the motor

 

response is slow, and the motor torque increases slowly. To control the response, set the value of J,

 

and then adjust the speed response (H005/H205).

*4

In the modes of sensorless vector control, 0Hz-range sensorless vector control and vector control with

 

sensor, inverter may output reverse to given operation command in the low speed range as a nature of

 

those control. In case there is a specific inconvenience for example reverse rotation damage the

 

machine, enable the reverse run protection (b046). (see 4.2.101: Reverse run protection function)

Arbitrary setting of motor constants

For the arbitrary setting of the motor constants, the function codes requiring settings vary depending on the settings of the 1st/2nd control function and the motor constant selection.

-When the 1st/2nd control function is enabled and "00" is specified for the motor constant selection Directly input the desired values for "H020" to "H024".

-When the 1st/2nd control function is enabled and "01" or "02" is specified for the motor constant

selection Directly input the desired values for "H030" to "H034".

When the offline auto-tuning has not been performed, the constants (Hitachi general-purpose motor constants) of the motors in the same capacity class as the inverter have been set for "H030/H230" to "H034/H234".

4 - 88