Chapter 2 Installation and Wiring

Digital (contact)

Analog

Analog input Relay contact output Open collector output Contact input

and logic switching

Status and alarm Status and factor

Function selection

Sensor

Symbol

Terminal name

Description

 

 

To switch the control logic between sink logic and source logic, change the

 

 

jumper connection of this (PLC) terminal to another terminal on the control

PLC

Intelligent input

circuit terminal block.

(common)

Jumper terminals P24 and PLC for the sink logic; jumper terminals CM1

 

and PLC for the sink logic.

 

 

 

 

To use an external power supply to drive the contact inputs, remove the

 

 

jumper, and connect the PLC terminal to the external interface circuit.

11

 

Select five of a total 51 functions, and assign these five functions to

 

terminals 11 to 15.

12

 

 

If you have selected an alarm code using the function "C062", terminals 11

13

Intelligent output

14

 

to 13 or 11 to 14 are used exclusively for the output of cause code for alarm

 

(e.g., inverter trip). The control logic between each of these terminals and

15

 

 

the CM2 terminal always follows the sink or source logic.

 

 

CM2

Intelligent output

This terminal serves as the common terminal for intelligent output terminals

(common)

[11] to [15].

 

 

 

Select functions from the 43 available, and assign the selected functions to

AL0

Intelligent relay

these terminals, which serve as C contact output terminals.

AL1

output

 

AL2

In the initial setting, these terminals output an alarm indicating that the

 

 

 

inverter protection function has operated to stop inverter output.

 

 

Connect to an external thermistor to make the inverter trip if an abnormal

 

 

temperature is detected.

 

 

The CM1 terminal serves as the common terminal for this terminal.

TH

External

[Recommended thermistor properties]

thermistor input

Allowable rated power: 100 mW or more

 

 

 

Impedance at temperature error: 3kH

 

 

The impedance to detect temperature errors can be adjusted within the

 

 

range 0H to 9,999H.

 

 

 

Electric property

Voltage drop between each terminal and CM2 when output signal is on: 4 V or less

Maximum allowable voltage: 27 VDC

Maximum allowable current: 50 mA (Maximum contact capacity)

AL1-AL0: 250 VAC, 2 A (resistance) or 0.2 A (inductive load) AL2-AL0: 250 VAC, 1 A (resistance) or 0.2 A (inductive load)

(Minimum contact capacity) 100 VAC, 10 mA

5 VDC, 100 mA Allowable range of input voltages

0 to 8 VDC [Input circuit]

 

DC8V

 

10kΩ

TH

1kΩ

Thermistor

 

CM1

 

(3)Explanation of switch settings

The internal slide switch (SW1) is used to enable or disable the emergency stop function (the function is disabled by factory setting).

* For the location of the slide switch, see page 2-9.