Hitachi SJ700-2 instruction manual Function Mode, Output frequency setting, Keypad Run key routing

Models: SJ700-2

1 274
Download 274 pages 15.86 Kb
Page 65
Image 65
Related code
b035: Rotational direction restriction
Related code F004: Keypad Run key routing
Related code
F001: Output frequency setting
A001: Frequency source setting A020/A220/A320:
Multispeed frequency setting, 1st/2nd/3rd motors
C001 to C008:
Terminal [1] to [8] functions
Chapter 4 Explanation of Functions

4.2 Function Mode

4.2.1 Output frequency setting

The output frequency setting function allows you to set the inverter output frequency.

You can set the inverter output frequency with this function (F001) only when you have specified "02" for the frequency source setting (A001). For other methods of frequency setting, see Section 4.2.4, "frequency source setting (A001)."

(If the setting of function "A001" is other than "02", function "F001" operates as the frequency command monitoring function.)

The frequency set with function "F001" is automatically set as the Multispeed frequency setting (A020). To set the second and third multispeed s, use the multispeed frequency setting, 2nd motor, function (A220) and multispeed frequency setting, 3rd motor, function (A320), or use function "F001" for the setting after turning on the SET and SET3 signals. For the setting using the SET and SET3 signals, assign the SET function (08) and SET3 function (17) to intelligent input terminals.

If the set output frequency is used as the target data for the PID function, PID feedback data will be displayed in percent (%). ("100%" indicates the maximum frequency.)

Item

Function code

Range of data

Description

Output frequency setting

F001

0.0, start frequency to

The frequency set with F001 is equal to the

 

 

setting of A020.

 

A020/A220/

maximum frequency,

The second control frequency set with F001

Multispeed 0

1st/2nd/3rd motors

is equal to the setting of A220.

A320

 

(Hz)

The third control frequency set with F001 is

 

 

 

 

 

equal to the setting of A320.

4.2.2 Keypad Run key routing

When you enter operation commands via the digital operator, the Keypad Run key routing function allows you to select the direction of motor operation.

This function is ineffective when you use the control terminal block or remote operator to input operation commands.

Item

Function code

Data

Description

Keypad Run key routing

F004

00

Forward operation

01

Reverse operation

 

 

4.2.3 Rotational direction restriction

The rotational direction restriction function allows you to restrict the direction of motor operation.

This function is effective regardless of the specification of operation command input device (e.g., control circuit block or digital operator).

If an operation command to drive the motor in a restricted direction is input, the inverter (digital operator)

will display .

Item

Function code

Data

Description

Rotational direction

b035

00

Both forward and reverse operations are enabled.

01

Only forward operation is enabled.

restriction

 

02

Only reverse operation is enabled.

 

 

4 - 7

Page 65
Image 65
Hitachi SJ700-2 Function Mode, Output frequency setting, Keypad Run key routing, Rotational direction restriction