Related code
b039: Automatic user-parameter setting function enable
U001 to U012: User parameters

Chapter 4 Explanation of Functions

4.2.86 Automatic user-parameter setting

The automatic user-parameter setting function allows you to make the inverter automatically store the parameters you readjusted sequentially as user parameters "U001" to "U012". You can use the stored data as a readjustment history. To enable this function, select "01" (enabling automatic user-parameter setting) for the automatic user-parameter setting function enable (b039).

The setting data entered in (displayed on) the digital operator is stored when the STR key is pressed. Also the monitor screen code (d***) is stored at the same time.

User parameter "U001" retains the latest update of setting; user parameter "U012", the oldest update. A functional parameter can be stored as only a single user parameter. After all the 12 user parameters have been used to store functional-parameter settings, new functional-parameter settings will be stored as user parameters on a first-in, first-out basis (that is, the next parameter will be written to "U012", storing the oldest update, first).

Item

Function code

Data

 

Description

Automatic user-parameter setting

b039

00

Disabling automatic user

function enable

01

Enabling automatic user

 

4.2.87 Stabilization constant setting

 

 

Related code

 

 

H006/H206/H306: Motor stabilization

The stabilization constant setting function allows you to adjust the inverter

constant, 1st/2nd/3rd motors

A045: V/f gain setting

to stabilize the motor operation when the motor operation is unstable.

b083: Carrier frequency setting

If the motor operation is unstable, check the motor capacity setting (H003/H203) and motor pole setting (H004/H204) to determine whether the settings match the motor specifications. If they do not match, readjust the settings. If the primary resistance of the motor is less than the standard motor specification, try to increase the setting of "H006/H206/H306" step by step. Try to reduce the setting of "H006/H206/H306" if the inverter is driving a motor of which the capacity is higher than the inverter rating.

You can also use the following methods to stabilize the motor operation:

1)Reducing the carrier frequency (b083) (See Section 4.2.11.)

2)Reducing the V/f gain setting (A045) (See Section 4.2.17.)

Item

Function code

Data

Description

Stabilization constant

H006/H206/

0. to 255.

Increase or reduce the setting to stabilize

H306

the motor.

 

 

V/f gain setting

A045

20. to 100. (%)

Reduce the setting to stabilize the motor.

Carrier frequency setting

b083

0.5 to 15.0 (kHz)

Reduce the setting to stabilize the motor.

4.2.88 Selection of operation at option board error

You can select how the inverter operates when an error results from a built-in option board between two modes. In one mode, the inverter trips. In the other mode, the inverter ignores the error and continues the operation.

When you use the feedback option board (SJ-FB) as option board 1, specify "01" for "P001". When you use the SJ-FB as option board 2, specify "01" for "P002".

Related code

P001: Operation mode on expansion card 1 error

P002: Operation mode on expansion card 2 error

Item

Function code

Data

Description

Operation mode on

P001/P002

00

TRP: Alarm output

expansion card 1 and 2

01

RUN: Continuation of operation

errors

 

 

 

 

 

4 - 79

Page 137