(ii) List of registers (frequency settings and trip monitoring)

Register

Function name

Function

R/W

Monitoring and setting items

Data

No.

code

resolution

 

 

 

0001h

Frequency source setting

F001 (high)

R/W

0 to 40000 (valid when A001 = 03)

0.01 [Hz]

0002h

F001 (low)

R/W

 

 

 

 

 

 

 

0: Initial status, 1: Waiting for Vdc establishment,

 

 

 

 

 

2: Stopping, 3: Running, 4: Free-run stop (FRS),

 

0003h

Inverter status A

-

R

5: Jogging, 6: DC braking, 7: Frequency being

-

 

 

 

 

input, 8: Retrying operation, 9: Undervoltage

 

 

 

 

 

(UV),

 

0004h

Inverter status B

-

R

0: Stopping, 1: Running, 2: Tripping

-

 

 

 

 

0: ---, 1: Stopping, 2: Decelerating, 3:

 

 

 

 

 

Constant-speed operation, 4: Accelerating, 5:

 

 

 

 

 

Forward rotation, 6: Reverse rotation, 7:

-

0005h

Inverter status C

-

R

Switching from forward rotation to reverse

 

 

 

 

rotation, 8: Switching from reverse rotation to

 

 

 

 

 

forward rotation, 9: Starting forward rotation, 10:

 

 

 

 

 

Starting reverse rotation

 

0006h

PID feedback

-

R/W

0 to 10000

0.01 [%]

0007h

 

 

 

 

 

to

(Reserved)

-

R

Inaccessible

-

0010h

 

 

 

 

 

0011h

Trip Counter

d080

R

0 to 65530

1 [time]

0012h

Trip monitoring 1 (factor)

 

 

See the list of inverter trip factors below

-

0013h

Trip monitoring 1 (inverter status)

 

 

See the list of inverter trip factors below

-

0014h

Trip monitoring 1 (frequency) (high)

 

 

0 to 40000

0.01 [Hz]

0015h

Trip monitoring 1 (frequency (low)

 

 

 

 

 

 

0016h

Trip monitoring 1 (current)

d081

R

Output current at tripping

0.1 A

0017h

Trip monitoring 1 (voltage)

DC input voltage at tripping

1 V

 

 

0018h

Trip monitoring 1 (running time) (high)

 

 

Cumulative running time at tripping

1h

0019h

Trip monitoring 1 (running time) (low)

 

 

 

 

 

 

001Ah

Trip monitoring 1 (power-on time) (high)

 

 

Cumulative power-on time at tripping

1h

001Bh

Trip monitoring 1 (power-on time) (low)

 

 

 

 

 

 

001Ch

Trip monitoring 2 (factor)

 

 

See the list of inverter trip factors below

-

001Dh

Trip monitoring 2 (inverter status)

 

 

See the list of inverter trip factors below

-

001Eh

Trip monitoring 2 (frequency) (high)

 

 

0 to 40000

0.01 [Hz]

001Fh

Trip monitoring 2 (frequency (low)

 

 

 

 

 

 

0020h

Trip monitoring 2 (current)

d082

R

Output current at tripping

0.1 A

0021h

Trip monitoring 2 (voltage)

DC input voltage at tripping

1 V

 

 

0022h

Trip monitoring 2 (running time) (high)

 

 

Cumulative running time at tripping

1h

0023h

Trip monitoring 2 (running time) (low)

 

 

 

 

 

 

0024h

Trip monitoring 2 (power-on time) (high)

 

 

Cumulative power-on time at tripping

1h

0025h

Trip monitoring 2 (power-on time) (low)

 

 

 

 

 

 

0026h

Trip monitoring 3 (factor)

 

 

See the list of inverter trip factors below

-

0027h

Trip monitoring 3 (inverter status)

 

 

See the list of inverter trip factors below

-

0028h

Trip monitoring 3 (frequency) (high)

 

 

0 to 40000

0.01 [Hz]

0029h

Trip monitoring 3 (frequency (low)

 

 

 

 

 

 

002Ah

Trip monitoring 3 (current)

d083

R

Output current at tripping

0.1 A

002Bh

Trip monitoring 3 (voltage)

DC input voltage at tripping

1 V

 

 

002Ch

Trip monitoring 3 (running time) (high)

 

 

Cumulative running time at tripping

1h

002Dh

Trip monitoring 3 (running time) (low)

 

 

 

 

 

 

002Eh

Trip monitoring 3 (power-on time) (high)

 

 

Cumulative power-on time at tripping

1h

002Fh

Trip monitoring 3 (power-on time) (low)

 

 

 

 

 

 

0030h

Trip monitoring 4 (factor)

 

 

See the list of inverter trip factors below

-

0031h

Trip monitoring 4 (inverter status)

 

 

See the list of inverter trip factors below

-

0032h

Trip monitoring 4 (frequency) (high)

 

 

0 to 40000

0.01 [Hz]

0033h

Trip monitoring 4 (frequency (low)

 

 

 

 

 

 

0034h

Trip monitoring 4 (current)

d084

R

Output current at tripping

0.1 A

0035h

Trip monitoring 4 (voltage)

DC input voltage at tripping

1 V

 

 

0036h

Trip monitoring 4 (running time) (high)

 

 

Cumulative running time at tripping

1h

0037h

Trip monitoring 4 (running time) (low)

 

 

 

 

 

 

0038h

Trip monitoring 4 (power-on time) (high)

 

 

Cumulative power-on time at tripping

1h

0039h

Trip monitoring 4 (power-on time) (low)

 

 

 

 

 

 

4 - 141