Hitachi SJ700-2 External analog input O/OI/O2 filter setting, 16 V/f gain setting

Models: SJ700-2

1 274
Download 274 pages 15.86 Kb
Page 73
Image 73
Maximum frequency for reverse operation
Related code
A016: External frequency filter time const.

Chapter 4 Explanation of Functions

(2) Start/end frequency settings for the O2-L terminal

Item

Function code

Range of data

Description

Remarks

02 start frequency

A111

-400. to 400.(Hz)

Setting of the start frequency

 

02 end frequency

A112

-400. to 400.(Hz)

Setting of the end frequency

 

02 start-frequency

A113

-100. to 100.(%)

Setting of the rate of the start frequency

 

to the external frequency command (-10

(Example 3)

rate

 

 

to +10 V) (*1)

 

 

 

 

02 end-frequency

 

 

Setting of the rate of the end frequency

 

A114

-100. to 100.(%)

to the external frequency command (-10

 

rate

 

 

 

to +10 V) (*1)

 

 

 

 

 

*1 The frequency rates correspond to the voltages (-10 to +10 V) of the external frequency command as follows:

-10 to 0 V: -100% to 0%

0 to +10 V: 0% to 100%

For example, if the voltage of the signal to be input to the O2-L terminal is -5 to +5 V, specify 50% for "A114".

(Example 3)

Maximum frequency for forward operation

(-10V) A112 -100% A113

 

 

 

 

Analog input

A114

100%

A111

(+10V)

(O2)

4.2.15 External analog input (O/OI/O2) filter setting

The external analog input filter setting function allows you to set the input-voltage/input-current sampling time to be applied when frequency commands are input as external analog signals.

You can use this filter function effectively for removing noise from the frequency-setting circuit signal.

If the noise disables the stable operation of the inverter, increase the setting. Setting a larger value makes the inverter response slower. The filtering constant is "set value (1 to 30) x 2 ms."

When the setting is "31" (factory setting), a hysteresis of ±0.1 Hz is added to the filtering constant (500 ms).

Item

Function code

Range of data

Description

External frequency filter

A016

1. to 30. or 31.

Setting of 1. to 30.: "Set value x 2" ms filter

Setting of 31.: 500 ms filter (fixed) with hysteresis

time const.

 

 

of ±0.1 Hz

 

 

 

4.2.16 V/f gain setting

The V/f gain setting function allows you to change the inverter output voltage by specifying the rate of the output voltage to the voltage (100%) selected with the AVR voltage select function (A082).

If the motor operation is cranky, try to increase the gain setting.

Related code

A045: V/f gain setting

A082: AVR voltage select

Item

Function code

Range of data

Description

V/f gain setting

A045

20. to 100. (%)

Setting of the rate of reducing the output voltage

AVR voltage select (100%)

A045

Base Maximum frequency frequency

4 - 15

Page 73
Image 73
Hitachi SJ700-2 instruction manual External analog input O/OI/O2 filter setting, 16 V/f gain setting