Chapter 4 Explanation of Functions

4.2.37 Dynamic braking (BRD) function

The dynamic braking (BRD) function is provided in the SJ700-220LFF/HFF and other models that have the built-in BRD circuit. With this function, the energy regenerated by the motor is consumed by an external resistor (i.e., the energy is converted to heat). You can effectively use this function in your system, for example, to operate the motor as a generator by rapidly decelerating the motor.

To use this function, make the following settings:

Related code

b090: Dynamic braking usage ratio

b095: Dynamic braking control

b096: Dynamic braking activation level

Item

Function code

Data or range of data

 

 

 

 

Description

 

 

 

 

 

0.0

Disabling the BRD operation

 

 

 

 

 

 

Setting of the dynamic braking usage ratio in units

 

 

 

of 0.1%

 

 

 

 

 

 

 

The inverter will trip when the set rate is exceeded.

 

 

 

 

t1

t2

 

t3

Dynamic braking

b090 (*2)

 

 

 

 

 

 

 

 

 

 

 

ON

ON

 

ON

usage ratio

0.1 to 100.0 (%)

 

 

 

 

 

 

 

 

BRD

100 seconds

 

 

 

 

 

 

operation

 

 

 

 

 

 

 

Usage rate (%) =

 

(t1+t2+t3)

100

 

 

 

 

 

 

 

 

 

100 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

Disabling the BRD operation

 

 

 

 

 

 

Enabling the BRD operation while the motor is

Dynamic braking

b095

01

running

 

 

 

 

Disabling the BRD operation while the motor is

control

 

 

 

stopped

 

 

 

 

 

 

 

 

 

 

 

 

 

02

Enabling the BRD operation regardless of whether

 

 

the motor is running

 

 

 

 

 

 

 

 

 

 

 

Dynamic braking

b096

330 to 380 (V) (*1)

Level setting for 200 V class models

 

 

activation level

660 to 760 (V) (*1)

Level setting for 400 V class models

 

 

 

 

 

*1 The set dynamic braking activation level specifies the DC output voltage of the inverter's internal converter.

*2 Please refer P2-22 for minimum resistance of connectable resistor and BRD ratio (2.2.5).

4.2.38 Cooling-fan operation setting

The cooling-fan operation setting function allows you to specify the operation mode of the inverter's internal cooling fan. The cooling fan can be operated on a constant basis or only while the inverter is driving the motor.

Related code

b092: Cooling fan control

Item

Function code

Data or range of data

Description

 

 

00

Specifying that the fan operates on a constant basis

Cooling fan

 

 

Specifying that the fan operates only while the

b092

 

inverter is driving the motor.

control

01

Note that the fan operates for 5 minutes after the

 

 

 

 

inverter power is turned on and after the inverter is

 

 

 

stopped.

Note: The cooling fan stops automatically when instantaneous power failure occurs or the inverter power is shut off and resume the operation after power recovered.

4 - 45