Frequency command
Related code
A069: Acceleration stop frequency setting
A070: Acceleration stop time frequency setting
Related code
A063: Jump (center) frequency setting 1
A064: Jump (hysteresis) frequency width setting 1
A065: Jump (center) frequency setting 2
A066: Jump (hysteresis) frequency width setting 2
A067: Jump (center) frequency setting 3
A068: Jump (hysteresis) frequency width setting 3
Chapter 4 Explanation of Functions

4.2.21 Jump frequency function

The jump frequency function allows you to operate the inverter so that it avoids the resonant frequency of the machine driven by the same.

Since the inverter avoids the motor operation with a constant output frequency within the specified range of the frequencies to jump when the jump frequency function is enabled, you cannot set any inverter output frequency within the specified range of the frequencies to jump.

Note that, while the inverter is accelerating or decelerating the motor, the inverter output frequency changes continuously according to the set acceleration/deceleration time.

You can set up to three frequencies to jump.

Item

Function code

Range of data

Description

Jump (center) frequency

A063/A065/

0.00 to 400.0 (Hz) (*1)

Setting of the center frequency of the

settings, 1st/2nd/3rd settings

A067

frequency range to be jumped

 

Jump (hysteresis) frequency

A064/A066/

 

Setting of the half bandwidth of the

width settings, 1st/2nd/3rd

0.00 to 10.00(Hz)

A068

frequency range to be jumped

settings

 

 

 

 

*1 Setting of 0 Hz disables the jump frequency function.

Output frequency

A067

A065

A066

A066

A068

A068

A063

A064

A064

4.2.22 Acceleration stop frequency setting

The acceleration stop frequency setting function allows you to make the inverter wait, upon starting the motor, until the slipping of the motor becomes less when the load on the motor causes a large moment of inertia.

Use this function if the inverter has tripped because of overcurrent when starting the motor.

This function can operate with every acceleration pattern, regardless of the setting of the acceleration curve selection (A097).

Item

Function code

Range of data

Description

Acceleration stop frequency

A069

0.00 to 400.0(Hz)

Setting of the frequency at which to

setting

stop acceleration

 

 

Acceleration stop time

A070

0.0 to 60.0(s)

Setting of the length of time to stop

frequency setting

acceleration

 

 

Output frequency

A069

A070

Frequency command

4 - 25

Page 83
Image 83
Hitachi SJ700-2 Jump frequency function, Acceleration stop frequency setting, Setting of the length of time to stop